Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: STORM KING PROPERTY MANAGEMENT, LTD

Foreign inspection · Safety discipline

On , OSHA opened a foreign safety inspection of STORM KING PROPERTY MANAGEMENT, LTD in 120 FRONT ST. THE TORCHES ON THE HUDSON, LLC, NEWBURGH, NY 12550 (NAICS 713930). OSHA activity number 336242789.

Watch Storm King Property Management, LTD — free Get an email when a new federal OSHA severe-injury report for Storm King Property Management, LTD is published. One employer, no account, unsubscribe in one click.
Site address
120 FRONT ST. THE TORCHES ON THE HUDSON, LLC
City
NEWBURGH
State
NY
ZIP
12550
Mailing
2899 ROUTE 9W, NEW WINDSOR, NY 12553
Inspection type
Foreign (L)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
713930
Employees
4
Ownership type
A

5 citations on file for this inspection.

1910.303 B01

Serious Gravity 10 1 instance 4 exposed
Issued
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1910.303(b)(1):  Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:    a) North Dock, 120 Front St. Newburgh, NY on or about 8/20/12, installed dock lighting was not free from recognized hazards in that design and installation of lighting and related components did not comply with applicable provisions of the National Electric Code.
Recent events (1)
  • — Z (S) $2800

1910.304 B02 III

Serious Gravity 5 2 instances 4 exposed
Issued
Penalty
Initial $2400.00 · Current $2400.00
29 CFR 1910.304(b)(2)(iii): The branch circuit wiring method did not include or provide an equipment grounding conductor to which the grounding contacts of the receptacle or cord could be connected:    a) North Dock, on or about 8/20/12, No equipment grounding conductor was installed at the galvanized steel light poles exposing employees to shock and burn hazards.     b) South dock, 120 Front St Newburgh, On or about 8/21/12, Extension cords were in use from the restaurant outdoor outlet to the dock with no ground pins.
Recent events (1)
  • — Z (S) $2400

1910.304 E01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $2000.00 · Current $2000.00
29 CFR 1910.304(e)(1)(i): Conductors and equipment rated 600 volts, nominal, or less were not protected from overcurrent in accordance with their ability to safely conduct current.    a) Northern Dock, The Torches on the Hudson, on or about 8/20/2012, the galvanized steel light poles had no over current protection for the circuit exposing employees to shock and burn hazards.
Recent events (1)
  • — Z (S) $2000

1910.305 A02 X

Serious Gravity 5 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $2400.00 · Current $2400.00
29 CFR 1910.305(a)(2)(x):  Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points:    a) South Dock 120 Front Street Dock On or about 8/21/12, an extension cord was plugged into an outdoor outlet at the restaurant and run underneath a concrete sidewalk, to the dock exposing it to damage.    b) North Dock, 120 Front Street Dock On or about 8/21/12, The power cord was worn down to bare copper wire resulting in electrifying the poles exposing employees to shock hazards.
Recent events (1)
  • — Z (S) $2400

1910.333 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1910.333(a)(1): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, in that:  Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:      a) North Dock, The Torches on Hudson, on or about 8/20/2012:  Employees were exposed to shock hazards while troubleshooting and repairing dock lighting and did not take adequate precautions to ensure equipment was denergized prior to contact.
Recent events (1)
  • — Z (S) $2800

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336242789.