Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NORTHWEST PALLET SUPPLY CO.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NORTHWEST PALLET SUPPLY CO. in 3648 MORREIM DR., BELVIDERE, IL 61008 (NAICS 321920). OSHA activity number 336299193.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Northwest Pallet Supply CO. — free Get an email when a new federal OSHA severe-injury report for Northwest Pallet Supply CO. is published. One employer, no account, unsubscribe in one click.
Site address
3648 MORREIM DR.
City
BELVIDERE
State
IL
ZIP
61008
Mailing
3648 MORREIM DR., BELVIDERE, IL 61008
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321920
Employees
200
Ownership type
A

5 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 1 instance 1 exposed
Issued
Mar 4, 2013
Penalty
Initial $2,295 · Current $1,607 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.    Miscellaneous Repair Area.  Metal electrical boxes with multiple outlets (110v) were used on the ends of flexible cables and hung above the work stations where employees plugged in portable tools such as Skil Saws.  The boxes had pre-punched knockouts, therefore exposing employees to electrical shock hazards.      There is no abatement documentation or certification required for this item.
Recent events (2)
  • — I (S) $1606.5
  • — Z (S) $2295

1910.334 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 4, 2013
Penalty
Initial $3,825 · Current $2,678 Reduced
29 CFR 1910.334(c)(1): Unqualified persons performed testing work on electric circuits or equipment.    Maintenance employees who performed live voltage measurements on equipment up to 480v were not qualified.    Abatement note:  Qualified persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment (PPE), insulating & shielding materials and insulated tools (see 1910.333(c)(2)).    There is no documentation or certification required for this item.
Recent events (2)
  • — I (S) $2677.5
  • — Z (S) $3825

1910.335 A01 V

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 4, 2013
Penalty
Initial $3,825 · Current $2,678 Reduced
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face:    Maintenance employees who performed live voltage measurements on equipment up to 480v while servicing and repairing equipment, did not wear face protection to prevent burns or injury from flying debris in the event of an arc flash or blast.    There is no abatement documentation or certification required for this item.    Abatement note:  For compliance assistance, refer to NFPA 70E national consensus standard "Standard for Electrical Safety in the Workplace, 2012 Edition", www.NFPA.org.
Recent events (2)
  • — I (S) $2677.5
  • — Z (S) $3825

1910.335 A01 I

Serious 1 instance 2 exposed
Issued
Mar 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i):  Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    Maintenance employees who performed live voltage measurements on equipment up to 480v while servicing and repairing equipment did not wear appropriate electrical protective equipment, including but not limited to the following, to protect against electrical shock and arc flash/blast injuries:    a)     Rubber insulating gloves with leather protectors.  b)     Arc-Rated clothing such as arc-rated long-sleeve shirt and pants or arc-rated coverall  c)     Hearing protection (canal inserts)  d)     Arc-rated flash suit hood or balaclava    There is no abatement documentation or certification required for this item.    Abatement Note:  For compliance assistance, refer to NFPA 70E national consensus standard "Standard for Electrical Safety in the Workplace, 2012 Edition", www.NFPA.org.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(iv): Employees exposed to the danger of head injury from electric shock or burns due to contact with exposed energized parts did not wear nonconductive head protection:    Maintenance employees who performed live voltage measurements on equipment up to 480v while servicing and repairing equipment did not wear nonconductive head protection, such as hard hats with die-electric properties, to protect against electrical shock and arc flash/blast injuries.    There is no abatement documentation or certification required for this item.    Abatement Note:  For compliance assistance, refer to NFPA 70E national consensus standard "Standard for Electrical Safety in the Workplace, 2012 Edition", www.NFPA.org.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Northwest Pallet Supply CO.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336299193.