CHELMSFORD, MA —
OSHA Inspection: API OF NH REALTY, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of API OF NH REALTY, LLC in 10 ELIZABETH DRIVE, CHELMSFORD, MA 01824 (NAICS 493110). OSHA activity number 336300587.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- API OF NH REALTY, LLC
- Site address
- 10 ELIZABETH DRIVE
- City
- CHELMSFORD
- State
- MA
- ZIP
- 01824
- Mailing
- 10 ELIZABETH DRIVE, CHELMSFORD, MA 01824
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 6
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.178 F02
- Issued
- Sep 28, 2012
- Abate by
- Oct 15, 2012
- Penalty
- Initial $3,500 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.178(f)(2): The storage and/or handling of liquid petroleum gas fuel was not in accordance with NFPA Storage and Handling of Liquid Petroleum Gases (NFPA 58-1969). (a) Location - 10 Elizabeth Drive, Chelmsford, MA: On or about 9/13/2012, the employer failed to ensure that propane tanks were stored ito prevent physical damage and tampering, and did impede the safe egress of occupants.
Recent events (2)
- — I (S) $2100
- — Z (S) $3500
1910.102 A
- Issued
- Sep 28, 2012
- Abate by
- Oct 15, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.102(a): The in-plant transfer, handling, storage, and utilization of acetylene in cylinders was not in accordance with Compressed Gas Association Pamphlet G-1-1966, which is incorporated by reference as specified in 29 CFR 1910.6. (a) Location - 10 Elizabeth Drive, Chelmsford, MA: On or about 9/13/2012, the employer failed to ensure that acetylene cylinders were stored in an area protected from moving objects and tampering.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.101 B
- Issued
- Sep 28, 2012
- Abate by
- Oct 15, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6. (a) Location - 10 Elizabeth Drive, Chelmsford, MA: On or about 9/13/2012, the employer failed to ensure that storage of compressed nitrogen cylinders were protected from heavy moving objects and tampering and the names of the gases being stored was not prominently listed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.178 L04 III
- Issued
- Sep 28, 2012
- Abate by
- Oct 12, 2012
- Penalty
- Initial $3,500 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years. (a) Location - 10 Elizabeth Street, Chelmsford, MA: On or about 9/13/2012,the employer failed to ensure that powered industrial truck operators received performance evaluations every three years.
Recent events (2)
- — I (S) $2100
- — Z (S) $3500
1910.178 Q07
- Issued
- Sep 28, 2012
- Abate by
- Oct 15, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(q)(7): Industrial trucks were not examined before being placed in service, or were placed in service if the examination showed conditions adversely affecting the safety of the vehicle. (a) Location - 10 Elizabeth Drive, Chelmsford, MA: On or about 9/13/2012, the employer failed to ensure that a powered industrial truck was examined prior to its use.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Sep 28, 2012
- Abate by
- Oct 15, 2012
- Penalty
- Initial $3,500 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed. (a) Location - 10 Elizabeth Drive, Chelmsford, MA: On or about 9/13/2012, the employer failed to ensure that unused openings in an electrical control panel were effectively closed.
Recent events (2)
- — I (S) $2100
- — Z (S) $3500
1910.303 G02 II
- Issued
- Sep 28, 2012
- Abate by
- Oct 15, 2012
- Penalty
- Initial $3,500 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage. (a) Location - Behind storage shelf, 10 Elizabeth Drive, Chelmsford, MA: On or about 9/13/2012, the employer failed to ensure that an exit sign was protected from physical damage.
Recent events (2)
- — I (S) $2100
- — Z (S) $3500
1910.303 G01 II
- Issued
- Sep 28, 2012
- Abate by
- Oct 15, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage. (a) Location - 10 Elizabeth Drive, Chelmsford, MA: On or about 9/13/2012, the employer failed to ensure that the areas directly in front of electrical control panels were not used for storage.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G02 I
- Issued
- Sep 28, 2012
- Abate by
- Oct 28, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): Location - 10 Elizbeth Street, Chemsford, MA: On or about 9/13/12, employer failed to guard live electrical parts from accidental contact.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 493110)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336300587.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.