MARTINSBURG, WV —
OSHA Inspection: U.S. DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of U.S. DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER in 510 BUTLER AVENUE, MARTINSBURG, WV 25401 (NAICS 622110). OSHA activity number 336318787.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER
- Site address
- 510 BUTLER AVENUE
- City
- MARTINSBURG
- State
- WV
- ZIP
- 25401
- Mailing
- 510 BUTLER AVENUE, MARTINSBURG, WV 25401
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 1619
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.335 B01
- Issued
- Feb 26, 2013
- Abate by
- Jun 21, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(b)(1): Safety signs, safety symbols, or accident prevention tags were not used where necessary to warn employees about electrical hazards which may endanger them, as required by 1910.145: a. Water Plant Well House. A 480 volt Square D motor starter electrical panel, was not labeled to inform employees of electrical arc hazards to which they may be exposed, as observed on January 23, 2013.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Feb 26, 2013
- Abate by
- Mar 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards were not provided with, and/or did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: a. Martinsburg VA Medical Center: Employees work on live electrical parts while troubleshooting energized equipment such as, but not limited to, the motor starter at the Water Plant Well House. Employees are exposed to 480 volts, and are not wearing appropriate electrical protective equipment such as, but not limited to, voltage rated gloves and flame resistant clothing, as determined on or about January 23, 2013. b. Martinsburg VA Medical Center: Employee(s) were exposed to live electrical part while obtaining the serial # and model # from inside the transformer located near the Heating Plant. Employee(s) were exposed to 480 volts and was not wearing appropriate electrical protective equipment such as, but not limited to, voltage rated gloves and flame resistant clothing, as determined on or about January 23, 2013. MARTINSBURG VA MEDICAL CENTER WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIVALENT STANDARD, 29 CFR 1910.335(A)(1)(I), WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 311680862, CITATION NUMBER 1 ITEM NUMBER 5, ISSUED ON AUGUST 4, 2010, AND ABATEMENT WAS CERTIFIED ON SEPTEMBER 30, 2010, WITH RESPECT TO A WORKPLACE LOCATED AT 510 BUTLER AVENUE, MARTINSBURG, WV. ABATEMENT CERTIFICATION AND DOCUMENTATION REQUIRED FOR THIS ITEM.
Recent events (2)
- — I (R) $0
- — Z (R) $0
1910.335 A01 IV
- Issued
- Feb 26, 2013
- Abate by
- Mar 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(iv): Employees exposed to the danger of head injury from electric shock or burns due to contact with exposed energized parts, did not wear nonconductive head protection: a. Martinsburg VA Medical Center: Employees work on live electrical parts while troubleshooting on energized equipment such as, but not limited to, the motor starter at the water plant well house. Employees were exposed to 480 volts, and were not wearing nonconductive head protection, as determined on or about January 22, 2013. b. Martinsburg VA Medical Center: Employee was exposed to live electrical parts while obtaining the serial # and model # from inside the transformer located near the Heating Plant. Employee was exposed to 480 volts and was not wearing nonconductive head protection, as determined on or about January 23, 2013. MARTINSBURG VA MEDICAL CENTER WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIVALENT STANDARD, 29 CFR 1910.335(A)(1)(IV), WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 311680862, CITATION NUMBER 1 ITEM NUMBER 7, ISSUED ON AUGUST 4, 2010, AND ABATEMENT WAS CERTIFIED ON SEPTEMBER 30, 2010, WITH RESPECT TO A WORKPLACE LOCATED AT 510 BUTLER AVENUE, MARTINSBURG, WV. ABATEMENT CERTIFICATION AND DOCUMENTATION REQUIRED FOR THIS ITEM.
Recent events (2)
- — I (R) $0
- — Z (R) $0
1910.335 A01 V
- Issued
- Feb 26, 2013
- Abate by
- Mar 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical equipment explosion did not wear protective equipment for the eyes or face: a. Martinsburg VA Medical Center: Employees work on live electrical parts while troubleshooting energized equipment such as, but not limited to, the motor starter at the Water Plant Well House. Employees were exposed to 480 volts, and were not wearing eye or face protection, as determined on or about January 22, 2013. b. Martinsburg VA Medical Center: Employee was exposed to live electrical parts while obtaining the serial # and model # from inside the transformer located near the Heating Plant. Employee was exposed to 480 volts, and was not wearing eye or face protection, as determined on or about January 23, 2013. MARTINSBURG VA MEDICAL CENTER WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIVALENT STANDARD, 29 CFR 1910.335(A)(1)(V), WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 311680862, CITATION NUMBER 1 ITEM NUMBER 6, ISSUED ON AUGUST 4, 2010, AND ABATEMENT WAS CERTIFIED ON SEPTEMBER 30, 2010, WITH RESPECT TO A WORKPLACE LOCATED AT 510 bUTLER AVENUE, MARTINSBURG, WV. ABATEMENT CERTIFICATION AND DOCUMENTATION REQUIRED FOR THIS ITEM.
Recent events (2)
- — I (R) $0
- — Z (R) $0
1910.335 A01 II
- Issued
- Feb 26, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(ii): Protective equipment was not periodically inspected or tested, as required in 1910.137: a. Martinsburg VA Medical Center: An electrician's high voltage (Class 2) lineman's rubber gloves have not been tested within the past 6 months, as determined on or about August 30, 2012. b. Martinsburg VA Medical Center: An electrician's low voltage (Class 00) lineman's rubber gloves have not been tested within the past 6 months, as determined on or about August 30, 2012. c. Martinsburg VA Medical Center: An electrician's high voltage (Class 2) lineman's rubber gloves have not been tested within the past 6 months, as determined on or about August 30, 2012. ABATEMENT CERTIFICATION AND DOCUMENTATION REQUIRED FOR THIS ITEM.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at U.S. Department of Veterans Affairs Medical Center
View U.S. Department of Veterans Affairs Medical Center's full OSHA safety record →
More inspections in this industry (NAICS 622110)
More inspections in WV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336318787.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.