WILMINGTON, DE —
OSHA Inspection: ALLAN A. MYERS LP
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ALLAN A. MYERS LP in 301 EAST 16TH ST., WILMINGTON, DE 19801 (NAICS 236220). OSHA activity number 336362181.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ALLAN A. MYERS LP
- Site address
- 301 EAST 16TH ST.
- City
- WILMINGTON
- State
- DE
- ZIP
- 19801
- Mailing
- 1805 BERKS RD., WORCESTER, PA 19490
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 595
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.34 C
- Issued
- Dec 3, 2012
- Abate by
- Dec 7, 2012
- Penalty
- Initial $2,295 · Current $2,295
General-duty citation text
29 CFR 1926.34(c): Means of egress was not continually maintained free of all obstructions or impediments to full instant use in the case of fire or other emergency: a) 301 East 16th St, Wilmington, DE A means of egress through the doorway was not continually maintained free from all obstructions or impediments to full instant use in the case of fire or other emergency. Two 100 feet energized (120 volts) temporary flexible cords were running across a doorway in the maintenance room to the hallway. 1 cord was used to energize a sump pump and 1 cord was energized but not being utilized, exposing the employees to a trip and fall hazard. This violation was observed on or about August 29, 2012.
Recent events (2)
- — I (O) $2295
- — Z (S) $2295
1926.152 E04
- Issued
- Dec 3, 2012
- Abate by
- Dec 7, 2012
- Penalty
- Initial $3,825 · Current $2,678 Reduced
General-duty citation text
29 CFR 1926.152(e)(4): Units dispensing flammable or combustible liquids were not protected against collision damage: a) 301 East 16th St, Wilmington, DE Construction site entrance The company had a 500 gallon double walled diesel fuel storage tank which was not protected from collision hazards. The fuel storage tank was positioned, approximately 30 feet from an active roadway, 15 feet from the roadway and 5 feet from the vehicle entrance to the jobsite, The company had wooden reflective signs and orange cones as barriers. This exposed the employees to fire/explosion hazards.The 500 gallon diesel fuel storage tank was on site to refuel heavy equipment and machinery. This violation was observed on or about August 29, 2012.
Recent events (2)
- — I (S) $2677.5
- — Z (S) $3825
1926.152 E01
- Issued
- Dec 3, 2012
- Abate by
- Dec 7, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.152(e)(1): Areas in which flammable combustible liquids were transferred at one time, in quantities greater than 5 gallons from one container to another were not provided with drainage or other means to control spills: a) 301 East 16th St, Wilmington, DE Construction site entrance The company had a 500 gallon double walled diesel fuel storage tank positioned, approximately 25 feet from the active roadway, 15 feet from the roadway and 5 feet from the entrance to the jobsite, which did not have drainage or other means to control spills. This violation was observed on or about August 29, 2012.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1926.405 A02 II I
- Issued
- Dec 3, 2012
- Abate by
- Dec 7, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(I): Protection was not provided to avoid damage to flexible cords and cables used for temporary wiring which passed through doorways or other pinch points: a) 301 East 16th St, Wilmington, DE Five 100 feet temporary energized (120 volts) flexible cords running through a doorway were not protected from damage. The company was using 3 of the cords to energize temporary lighting, 1 cord was used to energize a sump pump and 1 cord was energized but not being utilized. This exposed the employees to an electrical shock hazard. This violation was observed on or about August 29, 2012.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Allan a. Myers LP
View Allan a. Myers LP's full OSHA safety record →
More inspections in this industry (NAICS 236220)
More inspections in DE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336362181.