EL SEGUNDO, CA —
OSHA Inspection: DEFENSE COMMISSARY AGENCY - LOS ANGELES AFB B-251
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of DEFENSE COMMISSARY AGENCY - LOS ANGELES AFB B-251 in 483 NORTH AVIATION BLVD, EL SEGUNDO, CA 90245 (NAICS 445110). OSHA activity number 336401591.
Where did this inspection happen?
- Establishment
- DEFENSE COMMISSARY AGENCY - LOS ANGELES AFB B-251
- Site address
- 483 NORTH AVIATION BLVD
- City
- EL SEGUNDO
- State
- CA
- ZIP
- 90245
- Mailing
- 483 NORTH AVIATION BLVD, EL SEGUNDO, CA 90245
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 445110
- Employees
- 60
- Ownership type
- D
Citations
8 citations on file for this inspection.
1910.178 P01
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(p)(1): Where powered industrial trucks were found to be in need of repair, defective, or in any way unsafe, the trucks were not taken out of service until they had been restored to safe operating condition: Warehouse: On or about 10SEP12, 1518hrs, the charging cables were abraded exposing the conductors to employee contact. The sheathing was pulled back at connector end of the charging cable, exposing the conductors to operator contact.
Recent events (1)
- — Z (S) $0
1910.178 Q07
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(q)(7): Industrial trucks were not examined before being placed in service: Warehouse: On or about 10SEP12, 1518hrs, a motorized pallet jack was used on a daily basis without inspection for five days.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Meat managers office: On or about 10SEP12, 1532hrs, a power strip was used to provide 120VAC electrical service to another power strip.
Recent events (1)
- — Z (S) $0
1910.304 G05
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The paths to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective: Produce case: On or about 10SEPP12, 1539hrs, a two prong connector plug was taped to the end of a three prong ground flexible cord interrupting the path to ground.
Recent events (1)
- — Z (S) $0
1910.305 B01 II
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) Receiving door #13: On or about 10SEP12, at 1505hrs, 120VAC live conductors were exposed to inadvertent employee contact where a cover was left off an opening at the corner of an electrical box. (b) Receiving door #10: On or about 10SEP12, at 1505hrs, 120VAC live conductors were exposed to inadvertent employee contact where a cover was left off an opening at the corner of an electrical box.
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Break room: On or about 10SEP12, at 1525hrs, 120VAC a receptacle outlet box cover was broken exposing the 120VAC conductors to inadvertent employee contact.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure: (a) Secretary office: On or about 10SEP12, 1452hrs, a paper shredder was plugged into a flexible cord instead of the fixed wiring of the structure. (b) Secretary office: On or about 10SEP12, 1452hrs, a refrigerator was plugged into a flexible cord instead of the fixed wiring of the structure. (c) Produce case: On or about 10SEP12, 1539hrs, a water pump was plugged into a flexible cord instead of the fixed wiring of the structure.
Recent events (1)
- — Z (S) $0
1910.305 G02 II
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap: Produce case: On or about 10SEPP12, 1539hrs, a plug end was spliced to a flexible cord used to provide 120VAC service to a water pump.
Recent events (1)
- — Z (S) $0
More inspections in this industry (NAICS 445110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336401591.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.