OSHA Inspection: KENCO ELECTRIC INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of KENCO ELECTRIC INC. in 38281 HURRICANE DRIVE, WILLOUGHBY, OH 44094 (NAICS 238210). OSHA activity number 336414784.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Kenco Electric INC. — free Get an email when a new federal OSHA severe-injury report for Kenco Electric INC. is published. One employer, no account, unsubscribe in one click.
Establishment
KENCO ELECTRIC INC.
Site address
38281 HURRICANE DRIVE
City
WILLOUGHBY
State
OH
ZIP
44094
Mailing
8541 EAST AVENUE, MENTOR, OH 44060
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
12
Ownership type
A

3 citations on file for this inspection.

1926.403 I01 II

Serious Gravity 1 1 instance 3 exposed
Issued
Oct 10, 2012
Penalty
Initial $1,020 · Current $1,020
29 CFR 1926.403(i)(1)(ii):  Working space about electric equipment operating at 600 volts, nominal, or less was used for storage:    Construction-related equipment and other electric equipment including but not limited to ladders, saw(s), spools of wiring, and both empty and full cardboard  boxes of supplies for use at the site were stored in front of, and on top of, motor control units in the locked electrical room, rendering the units unaccessible.    Note: Readily accessible (as applied to equipment): "Capable of being reached quickly without requiring those to whom ready access is requisite to climb over or remove obstacles."
Recent events (1)
  • — Z (S) $1020

1926.405 A02 II C

Serious Gravity 1 1 instance 30 exposed
Issued
Oct 10, 2012
Penalty
Initial $1,020 · Current $1,020
29 CFR 1926.405(a)(2)(ii)(C): Receptacles for uses other than temporary lighting were installed on branch circuits which supplied temporary lighting:      At least one of the receptacles (quad box) powered both temporary lighting to the gym and also a shop vacuum and an extension cord that ended in a triple plug.
Recent events (1)
  • — Z (S) $1020

1926.403 H

Other-than-serious 1 instance 3 exposed
Issued
Oct 10, 2012
Abate by
Oct 13, 2012
Penalty
Initial $0 · Current $0
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident:    In the  motor control room, three terminated (completed) breakers were not labeled.