WILLOUGHBY, OH —
OSHA Inspection: KENCO ELECTRIC INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of KENCO ELECTRIC INC. in 38281 HURRICANE DRIVE, WILLOUGHBY, OH 44094 (NAICS 238210). OSHA activity number 336414784.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KENCO ELECTRIC INC.
- Site address
- 38281 HURRICANE DRIVE
- City
- WILLOUGHBY
- State
- OH
- ZIP
- 44094
- Mailing
- 8541 EAST AVENUE, MENTOR, OH 44060
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 12
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.403 I01 II
- Issued
- Oct 10, 2012
- Penalty
- Initial $1,020 · Current $1,020
General-duty citation text
29 CFR 1926.403(i)(1)(ii): Working space about electric equipment operating at 600 volts, nominal, or less was used for storage: Construction-related equipment and other electric equipment including but not limited to ladders, saw(s), spools of wiring, and both empty and full cardboard boxes of supplies for use at the site were stored in front of, and on top of, motor control units in the locked electrical room, rendering the units unaccessible. Note: Readily accessible (as applied to equipment): "Capable of being reached quickly without requiring those to whom ready access is requisite to climb over or remove obstacles."
Recent events (1)
- — Z (S) $1020
1926.405 A02 II C
- Issued
- Oct 10, 2012
- Penalty
- Initial $1,020 · Current $1,020
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(C): Receptacles for uses other than temporary lighting were installed on branch circuits which supplied temporary lighting: At least one of the receptacles (quad box) powered both temporary lighting to the gym and also a shop vacuum and an extension cord that ended in a triple plug.
Recent events (1)
- — Z (S) $1020
1926.403 H
- Issued
- Oct 10, 2012
- Abate by
- Oct 13, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident: In the motor control room, three terminated (completed) breakers were not labeled.
Recent events (1)
- — Z (O) $0
More inspections at Kenco Electric INC.
View Kenco Electric INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336414784.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.