THOUSAND OAKS, CA —
OSHA Inspection: NATIONAL PARK SERVICE - SANTA MONICA MOUNTAINS
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of NATIONAL PARK SERVICE - SANTA MONICA MOUNTAINS in DIAMOND X RANCH, THOUSAND OAKS, CA 91360 (NAICS 924120). OSHA activity number 336426002.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NATIONAL PARK SERVICE - SANTA MONICA MOUNTAINS
- Site address
- DIAMOND X RANCH
- City
- THOUSAND OAKS
- State
- CA
- ZIP
- 91360
- Mailing
- 401 WEST HILLCREST DR, THOUSAND OAKS, CA 91360
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 21
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.157 E02
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: Diamond X Ranch, Warehouse: On or about 11SEP12, 1502hrs, a fire extinguisher was not inspected monthly.
Recent events (1)
- — Z (S) $0
1910.157 E03
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: Diamond X Ranch, Warehouse: On or about 11SEP12, 1502hrs, a fire extinguisher was not inspected annually, lacking any record of annual inspection.
Recent events (1)
- — Z (S) $0
1910.242 B
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: Diamond X Ranch, Warehouse: On or about 11SEP12, 1502hrs, a portable air compressor used by the employees to clean the warehouse was not reduced to less than 30 p.s.i.:
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Diamond X Ranch, Roads & Trails office: On or about 11SEP12, 1357hrs, a power strip was used to provide 120VAC electrical service to another power strip. (b) Diamond X Ranch, Roads & Trails office: On or about 11SEP12, 1400hrs, a flexible cord was used to provide 120VAC service to another flexible cord.
Recent events (1)
- — Z (S) $0
1910.304 G05
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The paths to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective: Diamond X Ranch, ranch house bathroom: On or about 11SEP12, 1409hrs, a GFCI protected receptacle outlet had an open ground, interrupting the path to ground of the outlet.
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers identified for the purpose: Diamond X Ranch, Machine Shop: On or about 11SEP12, 1451hrs, the employer used duct tape to cover gaps left by a junction box cover that was not the correct size for the box.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure: Diamond X Ranch, Roads & Trails office: On or about 11SEP12, 1400hrs, an extension cord was used to provide power into the office on a permanent basis.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV D
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces: (a) Diamond X Ranch, Roads & Trails office: On or about 11SEP12, 1400hrs, flexible cords were attached to the building structure. (b) Diamond X Ranch, Machine Shop: On or about 11SEP12, 1437hrs, a power strip was attached to the building structure. (c) Diamond X Ranch, Warehouse: On or about 11SEP12, 1458hrs, two power strips were attached to the building structure near the workbench. (d) Diamond X Ranch, Warehouse: On or about 11SEP12, 1458hrs, flexible cords were attached to the building structure. (e) Diamond X Ranch, Warehouse: On or about 11SEP12, 1502hrs, a power strip was attached to the building structure near the air compressor.
Recent events (1)
- — Z (S) $0
1910.305 G02 II
- Issued
- Nov 6, 2012
- Abate by
- Nov 27, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap: Diamond X Ranch, Machine Shop: On or about 11SEP12, 1436hrs, a light bulb fixture was spliced to the end of a flexible cord to provide lighting and heating to a refrigerator.
Recent events (1)
- — Z (S) $0
More inspections at National Park Service - Santa Monica Mountains
View National Park Service - Santa Monica Mountains's full OSHA safety record →