CONSHOHOCKEN, PA —
OSHA Inspection: INTERSTATE GENERAL MEDIA
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of INTERSTATE GENERAL MEDIA in SCHUYLKILL PRINTING PLANT 800 RIVER ROAD, CONSHOHOCKEN, PA 19428 (NAICS 511110). OSHA activity number 336507991.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INTERSTATE GENERAL MEDIA
- Site address
- SCHUYLKILL PRINTING PLANT 800 RIVER ROAD
- City
- CONSHOHOCKEN
- State
- PA
- ZIP
- 19428
- Mailing
- 800 RIVER ROAD, CONSHOHOCKEN, PA 19428
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 511110
- Employees
- 1500
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.178 G02
- Issued
- Dec 6, 2012
- Penalty
- Initial $2,550 · Current $500 Reduced
General-duty citation text
29 CFR 1910.178(g)(2): Battery changing and charging installations for industrial trucks were not provided with facilities for flushing and neutralizing spilled electrolyte: a) Mailroom, Battery Charging Area - On or about September 13, 2012, where approximately 40 forklift battery charging stations are located, the spill kit was unmarked and blocked by pallets, effectively making the the flushing and neutralizing capabilities unavailable in the event of a spill.
Recent events (2)
- — I (S) $500
- — Z (S) $2550
1910.303 B02
- Issued
- Dec 6, 2012
- Penalty
- Initial $3,000 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Mail Room - On or about October 3, 2012, a relocatable power tap connected in tandem with an extension cord plugged into a dual receptacle outlet was used to provide power to appliances to include but not limited to a refrigerator and coffee maker. b) Engineering Services, Carpentry Area - On or about October 3, 2012, a cut-off saw was powered by a flexible cord plugged into a shop-made extension cord which was made from parts used in a manner in which they were not manufactured in that, the attachment plug was a quad junction box intended for permanent installation.
Recent events (2)
- — I (S) $2500
- — Z (S) $3000
1910.305 G01 IV
- Issued
- Dec 6, 2012
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv). (a) Machine Shop - On or about September 13, 2012, employees cut metal track with the Dake Cut-Off Saw where the flexible power cord was used as a substitute for the fixed wiring, in that it did not have an attachment plug and was run through a hole in floor.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.1200 H01
- Issued
- Dec 6, 2012
- Abate by
- Dec 26, 2012
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: a) Throughout Facility - On or about September 13, 2012, employees using hazardous chemicals, to include but not limited to battery acid, did not receive information and training regarding the hazards associated with chemicals.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.303 G01
- Issued
- Dec 6, 2012
- Penalty
- Initial $2,550 · Current $2,550
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) Engineering Services - On or about October 3, 2012, two electrical panel boxes were blocked in that paper and other combustible materials were piled on top of a desk located in front of and below the electrical cabinets.
Recent events (2)
- — I (S) $2550
- — Z (S) $2550
1910.147 C06 I
- Issued
- Dec 6, 2012
- Abate by
- Jan 3, 2013
- Penalty
- Initial $200 · Current $200
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: a) Throughout Facility - On or about October 18, 2012, where employees perform servicing and maintenance on equipment and energy control procedures have been developed and documented, an evaluation of each procedure has not been performed annually. INTERSTATE GENERAL MEDIA (FORMERLY PHILADELPHIA NEWSPAPERS) WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD OR ITS EQUIVALENT STANDARD 29 CFR 1910.147(C)(6)(i) WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 314722679, CITATION NUMBER 01, ITEM NUMBER 2A, AND WAS AFFIRMED AS A FINAL ORDER ON SEPTEMBER 30, 2011, WITH RESPECT TO A WORKPLACE LOCATED AT 800 RIVER ROAD, CONSHOHOCKEN, PENNSYLVANIA.
Recent events (2)
- — I (O) $200
- — Z (R) $200
1910.179 J02 III
- Issued
- Dec 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.179(j)(2)(iii): Monthly inspections of hooks, with a certification record which includes the date of inspection, the signature of the person who performed the inspection and the serial number, or other identifier, of the hook inspected, were not performed: a) Baler Area - On or about 09/13/2012, employees were using a 1/2 Ton Chain Hoist to load rolls of baling wire onto the baler with a damaged hook, in that the hook was twisted and the throat opening was expanded, not allowing the safety latch to contact the tip of the hook.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 511110)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336507991.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.