Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: HOSPITALITY VENTURES MANAGEMENT, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of HOSPITALITY VENTURES MANAGEMENT, LLC in 1300 NORTH ATLANTIC AVENUE, COCOA BEACH, FL 32931 (NAICS 721110). OSHA activity number 336566385.

Watch Hospitality Ventures Management, LLC — free Get an email when a new federal OSHA severe-injury report for Hospitality Ventures Management, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1300 NORTH ATLANTIC AVENUE
City
COCOA BEACH
State
FL
ZIP
32931
Mailing
1300 NORTH ATLANTIC AVENUE, COCOA BEACH, FL 32931
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
91
Ownership type
A

10 citations on file for this inspection.

1910.151 C

Serious Gravity 1 1 instance 9 exposed
Issued
Oct 23, 2012
Abate by
Nov 14, 2012
Penalty
Initial $2,550 · Current $1,530 Reduced
29 CFR 1910.151(c):   Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:    a) Laundry - No eyewash was available in the area where corrosive fluorosilicic acid was in use, on or about September 6, 2012.
Recent events (2)
  • — I (S) $1530
  • — Z (S) $2550

1910.332 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 23, 2012
Abate by
Nov 14, 2012
Penalty
Initial $4,250 · Current $2,550 Reduced
29 CFR 1910.332(b)(1):   Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    a) Resort-wide - No training was provided for maintenance employees who are required to work on live electrical parts and circuits, on or about September 26, 2012.
Recent events (2)
  • — I (S) $2550
  • — Z (S) $4250

1910.334 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 23, 2012
Abate by
Oct 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.334(c)(1):   Unqualified persons performed testing work on electric circuits or equipment.    a)  Engineering/Maintenance Shop - Employees were required to perform testing on 240 volts AC electrical circuits without being trained, on or about September 6, 2012.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 C02

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 23, 2012
Abate by
Oct 24, 2012
Penalty
Initial $4,250 · Current $2,550 Reduced
29 CFR 1910.333(c)(2):   Unqualified persons worked on energized circuit parts or equipment that had not been deenergized under the procedures of paragraph (b) of this section:    a)  In the Parking Lot - Power to a 120 volt AC outlet was not disconnected prior to changing it out, on or about September 6, 2012.
Recent events (2)
  • — I (S) $2550
  • — Z (S) $4250

1910.335 A01 I

Serious Gravity 5 2 instances 1 exposed
Issued
Oct 23, 2012
Abate by
Oct 24, 2012
Penalty
Initial $4,250 · Current $2,550 Reduced
29 CFR 1910.335(a)(1)(i):   Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    a)  In the Parking Lot - No protective equipment was worn while changing out a live 120 volt AC outlet, on or about September 6, 2012.    b)  In the Engineering/Maintenance Shop - No protective equipment was worn while troubleshooting live 240 volt AC circuits in a breaker box, on or about September 6, 2012.
Recent events (2)
  • — I (S) $2550
  • — Z (S) $4250

1910.335 A01 V

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 23, 2012
Abate by
Oct 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(v):     Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face:    a) Engineering/Maintenance Shop - No protective eye or face protection was worn while troubleshooting live 240 volt AC circuits in a breaker box, on or about September 6, 2012.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 E01

Serious Gravity 5 1 instance 9 exposed
Issued
Oct 23, 2012
Abate by
Nov 14, 2012
Penalty
Initial $3,400 · Current $2,040 Reduced
29 CFR 1910.1200(e)(1):   The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:    a)  Resort Wide - No written program was in place and employees were exposed to chemicals such as, but not limited to, fluorosilicic acid, on or about September 6, 2012.
Recent events (2)
  • — I (S) $2040
  • — Z (S) $3400

1910.1200 G08

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 23, 2012
Abate by
Nov 14, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(g)(8):     The employer did not maintain copies of the required material safety data sheets for each hazardous chemical in the workplace:    a)  Laundry - The sheet for the corrosive Ecolab Sour laundry chemical, containing twenty to fifty percent fluorosilicic acid, was missing, on or about September 6, 2012.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 H01

Serious 1 instance 3 exposed
Issued
Oct 23, 2012
Abate by
Nov 14, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(h)(1):     The employer did not provide employees with effective information and training on hazardous chemicals in their work area at the time of their initial assignment, and whenever a new physical or health hazard the employees had not previously been trained about was introduced into their work area:      a)  Laundry - An employee had not been instructed on the hazards of the corrosive Ecolab Sour laundry chemical, containing twenty to fifty percent fluorosilicic acid, on or about September 6, 2012.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.141 A03 I

Other-than-serious 4 instances 91 exposed
Issued
Oct 23, 2012
Abate by
Nov 14, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.141(a)(3)(i):     Places of employment were not kept clean to the extent that the nature of the work allowed:    a)  Captain's Grill Restaurant Dining Room and Kitchen - There was visible mold on several air diffusers, the walls and ceiling tiles, on or about September 6, 2012.    b)  Palm Room - There was visible mold on several air diffusers, on or about September 6, 2012.    c)  Commander's Club - There was visible mold on several air diffusers, the walls and ceiling tiles, on or about September 6, 2012.    d)  Guest Rooms in The Villa - There was visible mold on several air diffusers, on or about September 6, 2012.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336566385.