BATON ROUGE, LA —
OSHA Inspection: BATON ROUGE LODGING ASSOCIATES
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BATON ROUGE LODGING ASSOCIATES in COMFORT SUITES UNIVERSITY 3045 VALLEY CREEK DRIVE, BATON ROUGE, LA 70808 (NAICS 721110). OSHA activity number 336566393.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BATON ROUGE LODGING ASSOCIATES
- Site address
- COMFORT SUITES UNIVERSITY 3045 VALLEY CREEK DRIVE
- City
- BATON ROUGE
- State
- LA
- ZIP
- 70808
- Mailing
- 5701 PROGRESS ROAD, INDIANAPOLIS, IN 46241
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 20
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.303 G01
- Issued
- Oct 15, 2012
- Abate by
- Oct 25, 2012
- Penalty
- Initial $1,200 · Current $720 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. On or about 08/27/12 (During Hurricane Isaac), in an electrical closet on the north side of the hotel lobby, the employer allowed an employee to enter the electrical closet cluttered with stored items for the purpose of troubleshooting electrical equipment.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1910.305 B01 II
- Issued
- Oct 15, 2012
- Abate by
- Oct 25, 2012
- Penalty
- Initial $1,200 · Current $720 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. On or about 08/27/12 (during Hurricane Isaac), in the electrical closet on the north side of the hotel lobby, the employer allowed an employee to use breaker boxes (HB1, HB2, HA2) which were missing the "knock-out" covers over missing breakers in order to troubleshoot AC problems.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1910.157 C01
- Issued
- Oct 15, 2012
- Abate by
- Oct 25, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury. On 09/26/12, in the laundry room adjacent to the south side of the lobby, the employer allowed employees to work in an area where fire extinguishers were not mounted or marked.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 F02
- Issued
- Oct 15, 2012
- Abate by
- Oct 25, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. On or about 09/26/12, in the electrical closet on the north side of the hotel lobby, the employer allowed employees to access breaker boxes (LA3, LB2, LB3) which were not legibly marked in order to troubleshoot electrical problems.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1030 C01 I
- Issued
- Oct 15, 2012
- Abate by
- Oct 25, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1030(c)(1)(i): Each employer having an employee(s) with occupational exposure as defined by paragraph (b) of this section shall establish a written Exposure Control Plan designed to eliminate or minimize employee exposure. On 09/26/12 the employer did not possess a written Exposure Control Plan. The employer allowed employees to perform normal work functions (housekeeping, laundry, and maintenance) without a written plan in a hotel where used needles have been encountered during normal work functions.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 721110)
More inspections in LA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336566393.