POST FALLS, ID —
OSHA Inspection: EBENAL GENERAL INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of EBENAL GENERAL INC. in 3743 W. TAYJAN, POST FALLS, ID 83854 (NAICS 236116). OSHA activity number 336576582.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EBENAL GENERAL INC.
- Site address
- 3743 W. TAYJAN
- City
- POST FALLS
- State
- ID
- ZIP
- 83854
- Mailing
- PO BOX 31548, BELLINGHAM, WA 98228
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236116
- Employees
- 3
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.403 B02
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification. 3743 W. Tayjan, Post Falls, ID 83854; on or about 26 September 2012 and times prior thereto, a 120 volt, 4-plug junction box located on the second floor and a junction box located on a post next to the sidewalk were not used in accordance with the listing , labeling and or certification. A 120 volt, 4-plug junction box was wired to an extension cord. This condition exposed employees to a 120 volt electrical shock hazard.
Recent events (1)
- — Z (O) $0
1926.405 G02 IV
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws. 3743 W. Tayjan, Post Falls, ID 83854; on or about 26 September 2012 and times prior thereto, an orange extension cord was not connected to devices and fittings so that strain relief is provided. This condition exposed employees to an electrical shock and electrical burn hazards.
Recent events (1)
- — Z (O) $0
More inspections at Ebenal General INC.