Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DDI DENVER CORP.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of DDI DENVER CORP. in 10570 BRADFORD RD., LITTLETON, CO 80127 (NAICS 334412). OSHA activity number 336656186.

Watch DDI Denver Corp. — free Get an email when a new federal OSHA severe-injury report for DDI Denver Corp. is published. One employer, no account, unsubscribe in one click.
Establishment
DDI DENVER CORP.
Site address
10570 BRADFORD RD.
City
LITTLETON
State
CO
ZIP
80127
Mailing
10570 BRADFORD RD., LITTLETON, CO 80127
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
334412
Employees
103
Ownership type
A

5 citations on file for this inspection.

1910.303 B02

Other-than-serious 1 instance 8 exposed
Issued
Penalty
Initial $2890.00 · Current $2890.00
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.    a)  On or about August 29, 2012, and at times prior, employees were exposed to electrical shock because a power strip used in the plating area was connected to other extension cords or portable power outlets instead of directly to a permanently installed branch circuit receptacle.
Recent events (2)
  • — I (O) $2890
  • — Z (S) $2890

1910.303 C03 I

Other-than-serious 1 instance 8 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(c)(3)(i): All splices and joints and the free ends of conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose.    a)  On or about August 29, 2012, and at times prior, employees were exposed to electrical shock because wire splices for a solenoid in the tin plating area which were joined by wire nuts were not insulated nor contained in an enclosure or junction box to protect them from contact.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 G01 IV

Serious Gravity 5 2 instances 8 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv):  Flexibles cords and cables were used for purposes prohibited by subparagraphs (a) through (e) of this paragraph:     a)  On or about August 29, 2012, and at times prior, employees were exposed to electrical shock and fire hazards because flexible cords were used as a substitute for fixed wiring (conduit) along the walls in the preclean and plating areas.  In particular, flexible wiring was hardwired into a light switch which controlled a fan along the wall by the preclean tanks.      b)  On or about August 29, 2012, and at times prior, employees were exposed to electrical shock and fire hazards because flexible cords were attached to the building structure and surfaces such as pipe in the tin/lead plating area.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Deleted Serious Gravity 5 1 instance 8 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:                                                                 a)  On or about August 29, 2012, and at times prior, employees were exposed to electrical shock and fire hazards while they used a cord which powered a solenoid in the plating area which had strained and damaged insulation at the joint where the cord entered the plug.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.36 G02

Deleted Other-than-serious 1 instance 103 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.36(g)(2): An exit access was not at least 28 inches (71.1 cm) wide at all points:    a)  On or about August 29, 2012, the width of the exit access through the acid storage room was not at least 28 inches.  A pinch point existed between chemical barrels and a box which reduced the access width to 19 inches.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336656186.