Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,192,068Inspections Most recent open 2026-08-04 Last loaded 2026-08-07

OSHA Inspection: WEST ONE AND ASSOCIATES INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of WEST ONE AND ASSOCIATES INC. in 2203 N SAINT MARYS STREET # 1, SAN ANTONIO, TX 78212 (NAICS 423820). OSHA activity number 336676382.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch West ONE and Associates INC. for free Get an email when a new federal OSHA severe-injury report for West ONE and Associates INC. is published. One employer, no account, unsubscribe in one click.
Site address
2203 N SAINT MARYS STREET # 1
City
SAN ANTONIO
State
TX
ZIP
78212
Mailing
2203 N SAINT MARYS STREET # 1, SAN ANTONIO, TX 78212
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423820
Employees
15
Ownership type
A

4 citations on file for this inspection.

1910.242 A

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 30, 2012
Abate by
Dec 6, 2012
Penalty
Initial $1,600 · Current $960 Reduced
29 CFR 1910.242(a): Hand and portable powered tools or equipment were not kept in safe condition:    On or about 7/31/12, employees were exposed to an electrical hazard, while using a Metabo  2 speed impact drill (SBE 1040plus) mounted to a pipe cutter that had been modified without manufacturer approval.
Recent events (2)
  • · I (S) $960
  • · Z (S) $1600

1910.303 B07 I

Serious Gravity 1 1 instance 10 exposed
Issued
Nov 30, 2012
Abate by
Dec 10, 2012
Penalty
Initial $1,200 · Current $720 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:    On or about 7/31/12, employees were exposed to an electrical hazard from missing knockouts in an electrical outlet hanging in the the middle of the warehouse.
Recent events (2)
  • · I (S) $720
  • · Z (S) $1200

1910.303 B08 I

Serious Gravity 1 3 instances 12 exposed
Issued
Nov 30, 2012
Abate by
Dec 10, 2012
Penalty
Initial $1,200 · Current $720 Reduced
29 CFR 1910.303(b)(8)(i): Electric equipment was not firmly secured to the surface on which it was mounted:    On or about 7/31/12, employees were exposed to an electrical hazard from electrical outlets hanging from the ceiling and not being mounted in the middle of the warehouse.
Recent events (2)
  • · I (S) $720
  • · Z (S) $1200

1910.303 G02 I

Serious Gravity 10 2 instances 12 exposed
Issued
Nov 30, 2012
Abate by
Dec 10, 2012
Penalty
Initial $2,800 · Current $1,680 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    On or about 7/31/12, employees were exposed to an electrical hazard from live electrical wires hanging from the ceiling after removal of machinery in the middle of the warehouse.
Recent events (2)
  • · I (S) $1680
  • · Z (S) $2800

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336676382.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.