Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AT XPRESS, LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of AT XPRESS, LLC in 4141 LOCKBOURNE INDUSTRIAL, COLUMBUS, OH 43207 (NAICS 493110). OSHA activity number 336698592.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch At Xpress, LLC — free Get an email when a new federal OSHA severe-injury report for At Xpress, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
AT XPRESS, LLC
Site address
4141 LOCKBOURNE INDUSTRIAL
City
COLUMBUS
State
OH
ZIP
43207
Mailing
4141 LOCKBOURNE INDUSTRIAL, COLUMBUS, OH 43207
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
6
Ownership type
A

3 citations on file for this inspection.

1910.305 G01 IV

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 31, 2012
Abate by
Nov 30, 2012
Penalty
Initial $1,700 · Current $1,700
29 CFR 1910.305(g)(1)(iv):     Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used:    29 CFR 1910.305(g)(1)(iv)(A):     As a substitute for the fixed wiring of a structure;      a. At the workplace, the employer did not ensure that all stationary equipment was properly wired.  A pallet shrink wrap machine located near the bay doors on the loading dock, had an extension cord wiring into the control box and plugged into a near-by receptacle outlet, exposing employees to a fire hazard.
Recent events (1)
  • — Z (S) $1700

1910.305 G01 IV

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 31, 2012
Abate by
Nov 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv):     Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used:    29 CFR 1910.305(g)(1)(iv)(C):     Where run through doorways, windows, or similar openings;      a. At the workplace, the employer used an extension cord to charge a motorized pallet jack near the office.  The extension cord was ran from a 110v electrical receptable inside the office, through a door, to the motorized pallet jack outside the office, exposing employees to a shock hazard.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 1 1 instance 1 exposed
Issued
Oct 31, 2012
Abate by
Dec 14, 2012
Penalty
Initial $1,020 · Current $1,020
29 CFR 1910.305(g)(2)(iii):     Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.        a. At the workplace, the employer did not provide extensions cords that were free from defects, exposing employees to a shock hazard.  Employees used an extension cord to charge a motorized pallet jack.  The end of the extension cord had the strain relief pulled out of the plug.
Recent events (1)
  • — Z (S) $1020

View At Xpress, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336698592.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.