OAK HARBOR, WA —
OSHA Inspection: U.S. NAVY EXCHANGE MAINTENANCE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. NAVY EXCHANGE MAINTENANCE in S E TULAGI BUILDING 22, OAK HARBOR, WA 98278 (NAICS 493110). OSHA activity number 336712781.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. NAVY EXCHANGE MAINTENANCE
- Site address
- S E TULAGI BUILDING 22
- City
- OAK HARBOR
- State
- WA
- ZIP
- 98278
- Mailing
- 2110 N CORAL SEA AVE, OAK HARBOR, WA 98278
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 4
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.36 D01
- Issued
- Oct 23, 2012
- Abate by
- Dec 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: a) Electrician Room 29, where the designated exit door located across the hall was locked.
Recent events (1)
- — Z (S) $0
1910.37 B02
- Issued
- Oct 23, 2012
- Abate by
- Dec 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) At the facility, where the designated emergency exit doors not equipped with exit signs included: 1. Wood Shop 2. Break Room 3. Warehouse
Recent events (1)
- — Z (S) $0
1910.37 B04
- Issued
- Oct 23, 2012
- Abate by
- Dec 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
1910.37(b)(4): Where the direction of travel to the exit or exit discharge was not immediately apparent, signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge: a) Electrician Room 29, where directional signs were not posted along the exit access.
Recent events (1)
- — Z (S) $0
1910.37 B05
- Issued
- Oct 23, 2012
- Abate by
- Dec 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g., closet): a) Warehouse, where doors located in the exit access route were not equipped with signage included: 1. Compressor room door 2. Single door located adjacent to shelving 3. Double doors located adjacent to shelving
Recent events (1)
- — Z (S) $0
1910.213 B03
- Issued
- Oct 23, 2012
- Abate by
- Dec 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29CFR 1910.213(b)(3): On applications where injury to the operator might result if motors were to restart after power failures, provision was not made to prevent machines from automatically restarting upon restoration of power: a) Carpenter Shop, where wood working machines not equipped with anti-restart devices included: 1. Heavy Duty Milwaukee 8 inch panel saw, #6480. 2. Rockwell finishing sander, #NX7054. 3. Delta drill press
Recent events (1)
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Oct 23, 2012
- Abate by
- Dec 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors: a) Carpenter Shop, where an extension cord was run through the ceiling and used to supply power to the Heavy Duty Milwaukee 8 inch panel saw, #6480.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Oct 23, 2012
- Abate by
- Dec 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling: a) Electrician Room 29, where a relocatable power tap was used to supply power to appliances including, the Quasar microwave oven and the Mr. Coffee drip coffee maker. The U.S. Navy Exchange was previously cited for a violation of this standard which was contained in OSHA inspection no. 309093524, citation no. 1, item no. 1, issued on June 6, 2008 with respect to a workplace at Oak Harbor, WA.
Recent events (1)
- — Z (R) $0
1910.157 E02
- Issued
- Oct 23, 2012
- Abate by
- Dec 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: a) Maintenance Building 22, where employees would be expected to fight incipient stage fires, the Amerex fire extinguishers were not inspected on a monthly basis.
Recent events (1)
- — Z (O) $0
1910.303 G01 II
- Issued
- Oct 23, 2012
- Abate by
- Dec 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage: a) Warehouse, where the Jet Metal Cutting Band Saw was stored in front of circuit panel P5.
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 493110)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336712781.