Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ABC PALLET

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ABC PALLET in 6300 ST. LOUIS AVENUE, SAINT LOUIS, MO 63121 (NAICS 321920). OSHA activity number 336715586.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ABC Pallet — free Get an email when a new federal OSHA severe-injury report for ABC Pallet is published. One employer, no account, unsubscribe in one click.
Establishment
ABC PALLET
Site address
6300 ST. LOUIS AVENUE
City
SAINT LOUIS
State
MO
ZIP
63121
Mailing
6300 ST. LOUIS AVENUE, SAINT LOUIS, MO 63121
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321920
Employees
15
Ownership type
A

3 citations on file for this inspection.

1910.304 G05

Serious Gravity 1 1 instance 12 exposed
Issued
Nov 9, 2012
Abate by
Nov 30, 2012
Penalty
Initial $1,020 · Current $510 Reduced
29 CFR 1910.304(g)(5):     Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.    a) Inside of the employee break room, ABC Pallet employees were using a General Electric refrigerator that was not grounded. The metal casing (framing) on the appliance was energized.
Recent events (2)
  • — I (S) $510
  • — Z (S) $1020

1910.305 B01 I

Serious Gravity 1 2 instances 12 exposed
Issued
Nov 9, 2012
Abate by
Nov 30, 2012
Penalty
Initial $1,020 · Current $510 Reduced
29 CFR 1910.305(b)(1)(i):     Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed.    1. Outside of the employee break room, on the south wall, there was a 120/240 volt electrical panel box with an unused opening located inside. Employees were exposed to physical contact with live parts.    2. Outside of the employee break room, on the west wall, there was a 120/240 volt electrical panel box with two (2) large unused openings located inside of the box. Employees were exposed to physical contact with live parts.
Recent events (2)
  • — I (S) $510
  • — Z (S) $1020

1910.178 L01 I

Other-than-serious 2 instances 12 exposed
Issued
Nov 9, 2012
Abate by
Jan 23, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.178(l)(1)(i):     The employer shall ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l).    1. At the time of the inspection, the company owner had employees operating a fork truck who had not been trained and/or certified to drive fork trucks. Employees are in the process of being trained through a special program offered by the state of Missouri.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336715586.