Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ARMY RESERVE 88TH REGIONAL SUPPORT COMMAND

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ARMY RESERVE 88TH REGIONAL SUPPORT COMMAND in 401 EAST ALEXANDER AVE. PIER 23, TACOMA, WA 98421 (NAICS 336611). OSHA activity number 336762984.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Army Reserve 88TH Regional Support Command — free Get an email when a new federal OSHA severe-injury report for Army Reserve 88TH Regional Support Command is published. One employer, no account, unsubscribe in one click.
Site address
401 EAST ALEXANDER AVE. PIER 23
City
TACOMA
State
WA
ZIP
98421
Mailing
401 EAST ALEXANDER AVE. PIER 23, TACOMA, WA 98421
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336611
Employees
22
Ownership type
D

5 citations on file for this inspection.

1910.107 B05 IV

Serious Gravity 5 1 instance 1 exposed
Issued
Jan 2, 2013
Abate by
Feb 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.107(b)(5)(iv): Space within the spray booth on the downstream and upstream sides of filters were not protected with approved automatic sprinklers:    (a) Spray booth did not have a fire surpression system installed.
Recent events (1)
  • — Z (S) $0

1910.305 B02

Serious Gravity 1 1 instance 1 exposed
Issued
Jan 2, 2013
Abate by
Feb 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2):  Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:    (a) Second floor break room on north end of building outlet on wall opposite door was missing a cover.
Recent events (1)
  • — Z (S) $0

1910.35

Other-than-serious 1 instance 1 exposed
Issued
Jan 2, 2013
Abate by
Feb 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.35:  Employer was not in compliance with the exit-route provisions of NFPA 101, Life Safety Code, 2009 edition, or the exit-route provisions of the International Fire Code, 2009 edition.(incorporated by reference, see section  1910.6).    (a) Employer was using exit stairs for storage such as but not limited to paint, cleaning supplies and equipment
Recent events (1)
  • — Z (O) $0

1910.37 B04

Other-than-serious 4 instances 1 exposed
Issued
Jan 2, 2013
Abate by
Feb 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:    (a) First floor south end of building exit sign is over door however when standing on the north end of hallway there is no sign to indicate there is an exit at the south end.    (b) Second floor south end of building exit sign is over door however when standing on the north end of hallway there is no sign to indicate there is an exit at the south end.    (c) Supply room on the first floor, when standing in any of the aisles there is no indication of where the exit is. One direction leads to exit other direction lead back into the building.    (d) Mail room/Receiving area has five doors none are marked exit or not an exit, only one door leads to the exit.
Recent events (1)
  • — Z (O) $0

1910.37 B05

Other-than-serious 1 instance 1 exposed
Issued
Jan 2, 2013
Abate by
Feb 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):    (a) Mail room/Receiving area has five doors none are marked exit or not an exit, only one door leads to the exit.