HUNTSVILLE, AL —
OSHA Inspection: AVAILABLE PLASTICS, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of AVAILABLE PLASTICS, INC. in 5020 BEECHMONT DRIVE, HUNTSVILLE, AL 35811 (NAICS 326122). OSHA activity number 336816384.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AVAILABLE PLASTICS, INC.
- Site address
- 5020 BEECHMONT DRIVE
- City
- HUNTSVILLE
- State
- AL
- ZIP
- 35811
- Mailing
- 5020 BEECHMONT DRIVE, HUNTSVILLE, AL 35811
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326122
- Employees
- 75
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.95 C01
- Issued
- Dec 7, 2012
- Abate by
- Jan 28, 2013
- Penalty
- Initial $2,380 · Current $1,428 Reduced
81108111
General-duty citation text
29 CFR 1910.95(c)(1): The employer did not administer a continuing, effective hearing conservation program as described in 29 CFR 1910.9(c) through (o) whenever employee noise exposures equal or exceed an 8-hour time-weighted average sound level of 85 decibels measured on the A scale, or equivalently a dose of fifty percent: (a) On or about 10/11/12 - The Saw Operator on the automatic sealed air line was exposed to continuous noise at 149.4% of the allowable 8-hour time-weighted average sound level of 85 dBA or an equivalent level of 92.9 dBA. The sampling was performed for 437 minutes during one shift. Zero exposure was assumed for the unsampled time of 43 minutes. (b) On or about 10/11/12 - The Saw Operator on the manual sealed air line was exposed to continuous noise at 178.9% of the allowable 8-hour time-weighted average sound level of 85 dBA or an equivalent level of 94.2 dBA. The sampling was performed for 438 minutes during one shift. Zero exposure was assumed for the unsampled time of 42 minutes. (c) On or about 10/11/12 - The Saw Helper on the automatic sealed air line was exposed to continuous noise at 107.1% of the allowable 8-hour time-weighted average sound level of 85 dBA or an equivalent level of 90.5 dBA. The sampling was performed for 435 minutes during one shift. Zero exposure was assumed for the unsampled time of 45 minutes. (d) On or about 10/11/12 - The Regrind operator position was exposed to continuous noise at 108.7% of the allowable 8-hour time-weighted average sound level of 85 dBA or an equivalent level of 90.6 dBA. The sampling was performed for 382 minutes during one shift. Zero exposure was assumed for the unsampled time of 98 minutes.
Recent events (2)
- — I (S) $1428
- — Z (S) $2380
1910.212 A03 II
- Issued
- Dec 7, 2012
- Abate by
- Dec 27, 2012
- Penalty
- Initial $2,380 · Current $1,428 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): Point of operation guards were not designed and constructed as to prevent the operator from having any part of their body in the danger zone during the operating cycle: (a) On or about 10/11/12 - Fabrication Department, the saw blade was incompletely guarded on the manually operated sealed air saw.
Recent events (2)
- — I (S) $1428
- — Z (S) $2380
1910.242 B
- Issued
- Dec 7, 2012
- Abate by
- Dec 19, 2012
- Penalty
- Initial $1,785 · Current $1,071 Reduced
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: (a) On or about 10/11/12 - Fabrication Department in the sealed air saw area, the compressed air used to clean PVC chips from the machine and floor was measured at 70-80 psi.
Recent events (2)
- — I (S) $1071
- — Z (S) $1785
1910.305 G01 IV A
- Issued
- Dec 7, 2012
- Abate by
- Dec 19, 2012
- Penalty
- Initial $2,380 · Current $1,428 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) On or about 10/10/12 - Fabrication department, flexible cable was used to distribute power from the electrical panel box to the manual sealed air saw.
Recent events (2)
- — I (S) $1428
- — Z (S) $2380
1910.37 A03
- Issued
- Dec 7, 2012
- Abate by
- Dec 17, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: (a) On or about 10/10/12 - Extrusion buildings, a pvc water line was observed on the floor in the exit route.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.134 K06
- Issued
- Dec 7, 2012
- Abate by
- Dec 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(k)(6): The employer did not provide the basic advisory information on respirators, as presented in Appendix D of 29 CFR 1910.134, in written or oral format to employees who wear respirators when such use was not required by the employer: (a) On or about 10/10/12 - Fabrication department, employees used 3M 8210 face-filtering respirators when cutting and finishing pvc pipe and they had not been trained on the information in Appendix D.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.146 C02
- Issued
- Dec 7, 2012
- Abate by
- Dec 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.146(c)(2): The employer did not inform exposed employees, by posting danger signs or by any other equally effective means, of the existence and location of and the danger posed by the permit spaces: (a) On or about 10/10/12 - Five (5) silos containing PVC compound were not posted with a sign identifying them as a Permit Required Confined Space.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 F05 I
- Issued
- Dec 7, 2012
- Abate by
- Dec 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(5)(i): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the identity of the hazardous chemical(s) contained therein: (a) On or about 10/10/12 - Five (5) silos containing PVC compound were not labeled with the name of the material contained within the silos.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 F05 II
- Issued
- Dec 7, 2012
- Abate by
- Dec 19, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(5)(ii): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the appropriate hazard warnings: (a) On or about 10/10/12 - Five (5) silos containing PVC compound were not labeled with the hazard of the material contained within the silos.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Available Plastics, INC.
View Available Plastics, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 326122)
More inspections in AL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336816384.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.