OSHA Inspection: PILGRIM'S PRIDE CORPORATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PILGRIM'S PRIDE CORPORATION in 2045 HIGHWAY 244, RUSSELLVILLE, AL 35653 (NAICS 311615). OSHA activity number 337103782.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pilgrim'S Pride Corporation — free Get an email when a new federal OSHA severe-injury report for Pilgrim'S Pride Corporation is published. One employer, no account, unsubscribe in one click.
Site address
2045 HIGHWAY 244
City
RUSSELLVILLE
State
AL
ZIP
35653
Mailing
2045 HIGHWAY 244, RUSSELLVILLE, AL 35653
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311615
Employees
1346
Ownership type
A

4 citations on file for this inspection.

1910.119 D03 II

Other-than-serious 1 instance 2 exposed
Issued
Apr 15, 2013
Penalty
Initial $5,500 · Current $3,000 Reduced
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices:  (a) On or about 10/15/12 - At the High Pressure Receivers, a main shut-off valve HV 621 (king valve) was not identified with a prominent sign as specified in International Institute of Ammonia Refrigeration (IIAR) Bulletin No. 109 10/97, section 4.10.3.
Recent events (3)
  • — J (O) $3000
  • — C (S) $5500
  • — Z (S) $5500

1910.119 D03 I B

Deleted Other-than-serious 2 instances 2 exposed
Issued
Apr 15, 2013
Abate by
Apr 23, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process. (a) On or about 11/9/12 - at the Morris Chillers on the roof, the P&ID (Drawing No. PSM 23, Morrise Chiller) for chillers with a revision date of R4 8/16/11 was not accurate in that the Morris chiller identified as Rechiller 1 on the equipment was identified as RWC-4 (ME-15) on the drawing and as RWC-1A on the Refrigeration Department's red line drawing. (b) On or about 11/9/12 - at the Morris Chillers on the roof, the P&ID (Drawing No. PSM 23, Morrise Chiller) for chillers with a revision date of R4 8/16/11 was not accurate in that the Morris chiller identified as Rechiller 2 on the equipment was identified as RWC-3 (ME-14) on the drawing and as RWC-2A on the Refrigeration Department's red line drawing.
Recent events (3)
  • — J (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.22 A02

Other-than-serious 2 instances 4 exposed
Issued
Apr 15, 2013
Penalty
Initial $16,500 · Current $6,000 Reduced
29 CFR 1910.22(a)(2): Floor(s) of workroom(s) were not maintained in a clean and, so far as possible, a dry condition:  (a) On or about 10/25/12 - in the doorway between the High Stage and Vilter rooms, water was on the floor.  (b) On or about 10/25/12 - in the Vilter room, water was on the floor near the pumps for recirculator REC 2.  The employer, Pilgrim's Pride Corporation was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.22(a)(2), which was contained in OSHA inspection number 311948582, citation number 01, item number 001 and was affirmed as a final order on 6/1/2009, with respect to a workplace located at 2500 E. Lakeshore Drive, Waco, TX.
Recent events (3)
  • — J (O) $6000
  • — C (R) $16500
  • — Z (R) $16500

1910.305 G02 III

Deleted Repeat 1 instance 4 exposed
Issued
Apr 15, 2013
Penalty
Initial $220 · Current $0 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  (a) On or about 10/15/12 - in the Vilter room, the electric cord on the 110V drop down outlet used for power tools did not have strain relief.  The employer, Pilgrim's Pride Corporation was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(2)(iii), which was contained in OSHA inspection number 314198573, citation number 1, item number 23 and was affirmed as a final order on 5/12/2011, with respect to a workplace located at 2045 Highway 244, Russellville, AL.
Recent events (3)
  • — J (R) $0
  • — C (R) $220
  • — Z (R) $220

View Pilgrim'S Pride Corporation's full OSHA safety record →