MEADVILLE, PA —
OSHA Inspection: MALONEY PLASTICS, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MALONEY PLASTICS, INC. in 10940 MERCER PIKE, MEADVILLE, PA 16335 (NAICS 326199). OSHA activity number 337120182.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MALONEY PLASTICS, INC.
- Site address
- 10940 MERCER PIKE
- City
- MEADVILLE
- State
- PA
- ZIP
- 16335
- Mailing
- 10940 MERCER PIKE P.O. BOX 379, MEADVILLE, PA 16335
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 18
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 B01 I
- Issued
- Feb 1, 2013
- Abate by
- Feb 28, 2013
- Penalty
- Initial $3,500 · Current $2,625 Reduced
General-duty citation text
29 CFR 1910.303(b)(1)(i): Electric equipment was not free from recognized hazards that are likely to cause death or serious physical harm to employees in that, the safety of equipment was not determined for the suitability for installation and use in conformity with the provisions of this subpart: a) tool repair shop, southeast corner of building. On or about October 26, 2012, the receptacle outlet adjacent to the utility sink was not suitable for the wet or damp location and was not equipped with a ground-fault circuit interrupter.
Recent events (2)
- — I (S) $2625
- — Z (S) $3500
1910.305 J02 IV
- Issued
- Feb 1, 2013
- Abate by
- Feb 28, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: a) tool repair shop, southeast corner of building. On or about October 26, 2012, the receptacle outlet adjacent to the utility sink was not suitable for the location and was not equipped with a ground-fault circuit interrupter.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C07 IV
- Issued
- Feb 1, 2013
- Abate by
- Feb 28, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(iv): The employer did not certify that employee training has been accomplished and is being kept up to date: a) throughout the facility, on or about October 26, 2012, employee training on the Hazardous Energy Control Procedures (Lockout/Tagout Program) was not certified that it had been accomplished and was not up to date.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 326199)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337120182.