Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MALONEY PLASTICS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MALONEY PLASTICS, INC. in 10940 MERCER PIKE, MEADVILLE, PA 16335 (NAICS 326199). OSHA activity number 337120182.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Maloney Plastics, INC. — free Get an email when a new federal OSHA severe-injury report for Maloney Plastics, INC. is published. One employer, no account, unsubscribe in one click.
Site address
10940 MERCER PIKE
City
MEADVILLE
State
PA
ZIP
16335
Mailing
10940 MERCER PIKE P.O. BOX 379, MEADVILLE, PA 16335
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
18
Ownership type
A

3 citations on file for this inspection.

1910.303 B01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 1, 2013
Abate by
Feb 28, 2013
Penalty
Initial $3,500 · Current $2,625 Reduced
29 CFR 1910.303(b)(1)(i):    Electric equipment was not free from recognized hazards that are likely to cause death or serious physical harm to employees in that, the safety of equipment was not determined for the suitability for installation and use in conformity with the provisions of this subpart:    a)  tool repair shop, southeast corner of building.  On or about October 26, 2012, the receptacle outlet adjacent to the utility sink was not suitable for the wet or damp location and was not equipped with a ground-fault circuit interrupter.
Recent events (2)
  • — I (S) $2625
  • — Z (S) $3500

1910.305 J02 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 1, 2013
Abate by
Feb 28, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(iv):     A receptacle installed in a wet or damp location was not suitable for the location:    a)  tool repair shop, southeast corner of building.  On or about October 26, 2012, the receptacle outlet adjacent to the utility sink was not suitable for the location and was not equipped with a ground-fault circuit interrupter.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C07 IV

Other-than-serious 1 instance 13 exposed
Issued
Feb 1, 2013
Abate by
Feb 28, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(iv):     The employer did not certify that employee training has been accomplished and is being kept up to date:    a)  throughout the facility, on or about October 26, 2012, employee training on the Hazardous Energy Control Procedures (Lockout/Tagout Program) was not certified that it had been accomplished and was not up to date.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337120182.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.