Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: K & W TIRE COMPANY, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of K & W TIRE COMPANY, INC. in 6 WILLOW ROAD, AYER, MA 01432 (NAICS 441320). OSHA activity number 337170187.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch K & W Tire Company, INC. — free Get an email when a new federal OSHA severe-injury report for K & W Tire Company, INC. is published. One employer, no account, unsubscribe in one click.
Site address
6 WILLOW ROAD
City
AYER
State
MA
ZIP
01432
Mailing
6 WILLOW ROAD, AYER, MA 01432
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
441320
Employees
12
Ownership type
A

7 citations on file for this inspection.

1910.176 B

Serious Gravity 5 1 instance 12 exposed
Issued
Nov 29, 2012
Abate by
Jan 17, 2013
Penalty
Initial $4,500 · Current $2,700 Reduced
29 CFR 1910.176(b):     Material stored in tiers was not stacked, blocked, interlocked or limited in height so that it was stable and secure against sliding and collapse:    Location: Warehouse    On or about 10/31/12, employees working at the facility are exposed to rack collapse hazards in the following but not limited to areas;    - Rack B7  the second tier pallet was broken and three of the four corners of the racking were not secured to the pallet.
Recent events (2)
  • — I (S) $2700
  • — Z (S) $4500

1910.178 L03 II A

Serious Gravity 10 1 instance 12 exposed
Issued
Nov 29, 2012
Abate by
Jan 17, 2013
Penalty
Initial $6,300 · Current $3,780 Reduced
29 CFR 1910.178(l)(3)(ii)(A):     Powered industrial truck operators did not receive initial training on surface conditions where the vehicle would be operated:    Location:  Warehouse, loading dock    On or about 10/31/12, the employer did not train employees operating forklifts to ensure that the trailers were secured from movement prior to entering and exiting the trailers at the loading dock.
Recent events (2)
  • — I (S) $3780
  • — Z (S) $6300

1910.303 B06

Serious Gravity 10 1 instance 2 exposed
Issued
Nov 29, 2012
Abate by
Jan 17, 2013
Penalty
Initial $6,300 · Current $3,200 Reduced
29 CFR 1910.303(b)(6):     Conductors or equipment were located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that had a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures:    Location: Warehouse    On or about 10/31/12, an electrical cabinet was not designed to be exposed to wet conditions.
Recent events (2)
  • — I (S) $3200
  • — Z (S) $6300

1910.304 F01 VIII

Serious Gravity 5 2 instances 2 exposed
Issued
Nov 29, 2012
Abate by
Jan 17, 2013
Penalty
Initial $4,500 · Current $2,300 Reduced
29 CFR 1910.304(f)(1)(viii):     Circuit breakers for circuits rated 600 volts, nominal, or less used as switches in 120 volt and 227 volt fluorescent lighting circuits, were not listed and marked "SWD":    Location:  Warehouse    On or about 10/31/12, the breakers that were used as switches in the electrical cabinet were not marked SWD as required.
Recent events (2)
  • — I (S) $2300
  • — Z (S) $4500

1910.305 B01 II

Serious Gravity 10 2 instances 2 exposed
Issued
Nov 29, 2012
Abate by
Jan 17, 2013
Penalty
Initial $6,300 · Current $0 Reduced
29 CFR 1910.305(b)(1)(ii):     Unused openings in boxes, cabinets, or fittings were not effectively closed:    Location: Warehouse    Instance 1:  On or about 10/31/12, the electrical panel had unused openings that were not effectively closed exposing workers who turn the lights on and off in the warehouse to electrical shock and fire hazards.    Instance 2: On or about 10/31/12, a knockout was missing on the side of the electrical panel exposing employees to electrical shock and fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6300

1910.132 D02

Other-than-serious 1 instance 12 exposed
Issued
Nov 29, 2012
Abate by
Jan 17, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(2):     The employer did not verify, through a written certification, the identity of the workplace evaluated, the person certifying that the evaluation had been performed, and the date the hazard assessment was done:    Location: Warehouse    On or about 10/31/12, the employer did not certify the workplace of hazards through a written hazard assessment for the employees that wear safety harnesses while operating high reach powered industrial trucks.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 F02

Other-than-serious 2 instances 2 exposed
Issued
Nov 29, 2012
Abate by
Jan 17, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2):     Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    Location:  Warehouse    On or about 10/31/12, the breakers in the electrical cabinet were not legibly marked or labeled to indicate what each breakers purpose.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View K & W Tire Company, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337170187.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.