Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: VALOR SERVICES LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of VALOR SERVICES LLC in 1800 SOUTH VIRGINIA, PORT LAVACA, TX 77979 (NAICS 237120). OSHA activity number 337180996.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Valor Services LLC — free Get an email when a new federal OSHA severe-injury report for Valor Services LLC is published. One employer, no account, unsubscribe in one click.
Establishment
VALOR SERVICES LLC
Site address
1800 SOUTH VIRGINIA
City
PORT LAVACA
State
TX
ZIP
77979
Mailing
P O BOX 1336, EDNA, TX 77957
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237120
Employees
45
Ownership type
A

7 citations on file for this inspection.

1910.254 D07

Serious Gravity 1 1 instance 1 exposed
Issued
Dec 20, 2012
Penalty
Initial $1,517 · Current $910 Reduced
29 CFR 1910.254(d)(7):     Electrode holders when not in use were not so placed that they could not make electrical contact with persons, conducting objects, fuel or compressed gas tanks:      On or about November 1, 2012, in the main shop, employees performed single hand welding on a skid and were exposed to electric shock and impalement hazards from a welding rod left in a stinger and laying on the ground in the walking/working area.
Recent events (2)
  • — I (S) $910.2
  • — Z (S) $1517

1910.303 F02

Serious Gravity 5 3 instances 4 exposed
Issued
Dec 20, 2012
Penalty
Initial $2,023 · Current $1,214 Reduced
29 CFR 1910.303(f)(2):     Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    On or about November 1, 2012, in the main shop, employees operate flexible cord and plug tools and equipment during fabrication of oilfield skids and the circuit breakers in electrical panels were not identified such as but not limited to the following locations:    a)  Square D QO Load Center for the middle shop with five circuit breakers;     b)  Square D QO Load Center for the lighting with thirty-seven circuit breakers;    c)  Square D Rainproof Load Center at outside electric panel board with ten circuit breakers.
Recent events (2)
  • — I (S) $1213.8
  • — Z (S) $2023

1910.305 B01 II

Serious Gravity 5 3 instances 4 exposed
Issued
Dec 20, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii):     Unused openings in boxes, cabinets, or fittings were not effectively closed:    On November 1, 2012, at this establishment, employees used flexible cord and plug hand tools during the fabrication of oilfield skids and the electric panel boards had unused openings where energized conductors were exposed such as but not limited to:    a)  In the main shop, the Square D QO Load Center for the middle shop had one missing circuit breaker;    b)  In the outside yard, the Square D Rainproof Center had one missing circuit breaker;    c)  In the outside yard, the Square D Rainproof Center had one unused opening at the bottom of the panel where a conductor was missing.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 3 instances 2 exposed
Issued
Dec 20, 2012
Abate by
Dec 27, 2012
Penalty
Initial $2,975 · Current $1,785 Reduced
29 CFR 1910.305(b)(2)(i):     Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:    On or about November 1, 2012, in the main shop, employee's operated welding machines with flexible cords and plugs spliced to the receptacle outlet boxes wiring and the covers on the boxes were missing such as but not limited to the following:     a)  Receptacle outlet identified as Breaker #4.   b)  Receptacle outlet box identified as Breaker #1.  c)  Receptacle outlet box identified as Breaker #2.
Recent events (2)
  • — I (S) $1785
  • — Z (S) $2975

1910.305 J02 I

Serious Gravity 5 3 instances 2 exposed
Issued
Dec 20, 2012
Abate by
Dec 27, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(i):     Attachment plugs were installed so that their prongs, blades, or pins were energized when they were not inserted into an energized receptacle:    On or about November 1, 2012, in the main shop, employee's operated welding machines and the flexible cords and plugs had been removed and spliced to the receptacle outlet boxes wiring such as but not limited to the following machines:    a)  Flextec 450 Lincoln Electric welder, serial U1120111968, order 12810389.  b)  Flextec 450 Lincoln Electric welder, serial U1120204924, order 12828523.  c)  Flextec 450 Lincoln Electric welder, serial U11200205421, order 12831670.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.184 C01

Other-than-serious 1 instance 1 exposed
Issued
Dec 20, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.184(c)(1):     Sling(s) that were damaged or defective were used:    On or about November 1, 2012, in the main shop, employees used synthetic slings to move large steel skids around the work area and a sling was damaged and split throughout its length with the red safety cord exposed.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV C

Other-than-serious 1 instance 1 exposed
Issued
Dec 20, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(C):     Flexible cords and cables were run through doorways, windows, or similar openings:      On or about November 1, 2012, in the main shop, employees installing equipment onto a skid used a portable angle grinder connected to an extension cord which had been run through a doorway.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Valor Services LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337180996.