NORTH CHARLESTON, SC —
OSHA Inspection: ATLANTIC COAST MATERIALS, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ATLANTIC COAST MATERIALS, LLC in BETWEEN PIERS M AND N VETERANS TERMINAL, NORTH CHARLESTON, SC 29405 (NAICS 423320). OSHA activity number 337200018.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ATLANTIC COAST MATERIALS, LLC
- Site address
- BETWEEN PIERS M AND N VETERANS TERMINAL
- City
- NORTH CHARLESTON
- State
- SC
- ZIP
- 29405
- Mailing
- PO BOX 461, UPPERVILLE, VA 20185
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423320
- Employees
- 3
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.106 G03 IV D
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(g)(3)(iv)(d): The dispensing units, were not mounted either on a concrete island or protected against collision damage by suitable means. a) Southwest end of the worksite: A 500 gallon diesel fuel tank used to refuel vehicles and equipment was not protected from collision damage. ABATEMENT CERTIFICATION IS REQUIRED.
Recent events (1)
- — Z (O) $0
1910.106 G09
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(g)(9): Fire extinguisher(s) having a minimum approved classification of 6 B, C were not provided and located so as to be within 75 feet of each pump, dispenser, underground fill pipe opening, or lubrication or service room: a) Southwest end of the worksite: There was not at least one fire extinguisher located within 75 feet of a 500 gallon diesel fuel tank used to refuel vehicles and equipment at the site. ABATEMENT CERTIFIICATIN IS REQUIRED.
Recent events (1)