COLUMBUS, OH —
OSHA Inspection: ROYAL ELECTRIC
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of ROYAL ELECTRIC in 2020 JACKSON PIKE, COLUMBUS, OH 43223 (NAICS 238210). OSHA activity number 337270631.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ROYAL ELECTRIC
- Site address
- 2020 JACKSON PIKE
- City
- COLUMBUS
- State
- OH
- ZIP
- 43223
- Mailing
- 1250 MEMORY LANE N., COLUMBUS, OH 43209
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 25
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.405 B01
- Issued
- Dec 6, 2012
- Abate by
- Dec 26, 2012
- Penalty
- Initial $1,360 · Current $0 Reduced
General-duty citation text
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, or fittings. Conductors entering boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. Unused openings in cabinets, boxes, and fittings shall also be effectively closed. a. In the compressor area, there was a 480 volt energized electrical panel which had an unused opening in the panel thereby exposing employees to a contact hazard. b. On the east side of Shaft 1, there was a 2 inch unused opening in the bottom of the energized 120/208 electrical panel thereby exposing employees to a contact hazard. c. In the bottom of Shaft 2, there was an unused opening in the bottom of the 277/480 energized electrical panel thereby exposing employees to a contact hazard. d. On the south side of Shaft 6, there was an unused opening in the bottom of the energized 480 volt electrical panel thereby exposing employees to a contact hazard. e. On the east side of Shaft 6, their was an unused opening in the bottom of the energized electrical outlet box, thereby exposing employees to a contact hazard. f. On the north side of Shaft 6, there was an unused opening in the bottom of the energized 480 volt electrical panel, thereby exposing employees to a contact hazard. g. On the Neil Street location where tunneling was being performed, there was a unused opening in the electrical outlet box thereby exposing employees to a contact hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $1360
1926.416 E01
- Issued
- Dec 6, 2012
- Abate by
- Dec 26, 2012
- Penalty
- Initial $1,020 · Current $0 Reduced
General-duty citation text
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables shall not be used. a. On the Neil Road where electrical equipment was used to provide power for portable tools and lighting, the electrical cord to the outlet was worn and pulled from the electrical box thereby exposing employees to a contact hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $1020
1926.432 B
- Issued
- Dec 6, 2012
- Abate by
- Dec 26, 2012
- Penalty
- Initial $1,360 · Current $0 Reduced
General-duty citation text
29 CFR 1926.432(b): Protection against corrosion. Metal raceways, cable armor, boxes, cable sheathing, cabinets, elbows, couplings, fittings, supports, and support hardware shall be of materials appropriate for the environment in which they are to be installed. a. In Shaft 2 where electrical equipment was set up to provide power to equipment, tools and other lighting, protection was not provided over the electrical equipment in the shaft to keep water from getting inside the electrical equipment and causing corrosion on the electrical equipment thereby exposing employees to a contact hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $1360
More inspections at Royal Electric
View Royal Electric's full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337270631.