AIEA, HI —
OSHA Inspection: ANHEUSER BUSCH SALES OF HAWAII INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ANHEUSER BUSCH SALES OF HAWAII INC in 99-877 IWAENA ST, AIEA, HI 96701 (NAICS 424810). OSHA activity number 337318216.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ANHEUSER BUSCH SALES OF HAWAII INC
- Site address
- 99-877 IWAENA ST
- City
- AIEA
- State
- HI
- ZIP
- 96701
- Mailing
- 99-877 IWAENA ST, AIEA, HI 96701
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424810
- Employees
- 130
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.305 B02 I
- Issued
- Nov 21, 2012
- Penalty
- Initial $2,168 · Current $2,168
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: a) Open Warehouse: The cover on an electrical junction box, located near Dock #5, was not properly attached exposing the energized conductors to contact, as observed on or about November 9, 2012. Abatement Observed During Inspection.
Recent events (2)
- — I (O) $2168
- — Z (S) $2168
1910.305 J01 I
- Issued
- Nov 21, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact: a) Sales Room: A receptacle, being used to supply power to computers, was missing a cover exposing the energized electrical terminals to contact, as observed on or about November 9, 2012. Abatement Observed During Inspection
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.303 B07 IV
- Issued
- Nov 21, 2012
- Penalty
- Initial $2,890 · Current $2,890
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: a) Open Warehouse: Two sections of electrical conduct, located near Dock #5, were damaged exposing the conductors to contact, as observed on or about November 9, 2012. b) Outside Yard Area: Four electrical receptacles attached to the exterior of the building were damaged creating a potential shock hazard, as observed on or about November 9, 2012. Abatement Observed During Inspection
Recent events (2)
- — I (O) $2890
- — Z (S) $2890
1910.305 J02 IV
- Issued
- Nov 21, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: a) Outside Yard Area: Electrical receptacles, mounted to the exterior of the building, were not weatherproof in that the receptacle covers had been broken off, as observed on or about November 9, 2012. Abatement Observed During Inspection
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.304 F01 IV
- Issued
- Nov 21, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: a) Open Warehouse: An electrical panel board, located near the pallet jack battery chargers, was blocked by stored materials and equipment, as observed on or about November 9, 2012. Abatement Observed During Inspection
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Anheuser Busch Sales of Hawaii INC
View Anheuser Busch Sales of Hawaii INC's full OSHA safety record →
More inspections in this industry (NAICS 424810)
More inspections in HI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337318216.