FOUNTAIN, CO —
OSHA Inspection: UNITED RADIO FREQUENCY LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of UNITED RADIO FREQUENCY LLC in 6150 SOUTHMOOR DRIVE, FOUNTAIN, CO 80817 (NAICS 334419). OSHA activity number 337382220.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- UNITED RADIO FREQUENCY LLC
- Site address
- 6150 SOUTHMOOR DRIVE
- City
- FOUNTAIN
- State
- CO
- ZIP
- 80817
- Mailing
- 6150 SOUTHMOOR DRIVE, COLORADO SPRINGS, CO 80911
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 334419
- Employees
- 1
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 B07 I
- Issued
- Jan 10, 2013
- Abate by
- Feb 6, 2013
- Penalty
- Initial $1,600 · Current $1,600
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: (a) On or about November 15, 2012, and at times prior, employees were exposed hazards of live electrical components in the following locations because they were not effectively closed: 1) The electrical box mounted on the north wall which supplied power to an RF Generator Rack had a hole in the door. 2) Two plug boxes hanging from the ceiling had the face plate disconnected from the box and the live wires were out of the boxes. 3) A plug on the south wall in the lab area, labeled "Unit 1-CT.13," was missing a face plate. 4) The circuit breaker box mounted on the north wall of the building stood open. Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (1)
- — Z (S) $1600
1910.303 G01 II
- Issued
- Jan 10, 2013
- Abate by
- Feb 6, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: (a) On or about November 15, 2012, and at times prior, the area under and in front of the circuit breaker box had items stored in it. Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").
Recent events (1)
- — Z (S) $0
1910.334 A01
- Issued
- Jan 10, 2013
- Abate by
- Feb 6, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(1): Flexible electric cords were fastened with staples or otherwise hung in such a fashion as could damage the outer jacket or insulation: (a) On or about November 15, 2012, and at times prior, an employees was exposed to electrical hazards from an extension cord that was fastened to a light fixture with a zip tie. Abatement Note: Abatement certification is required for this item (see enclosed "Certification of Corrective Action Worksheet").