OSHA Inspection: U.S. DEPARTMENT OF VETERANS AFFAIRS - LOS ANGELES NATIONAL CEMETERY

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of U.S. DEPARTMENT OF VETERANS AFFAIRS - LOS ANGELES NATIONAL CEMETERY in 950 S. SEPULVEDA BLVD. ADMIN BLDG, LOS ANGELES, CA 90049 (NAICS 812220). OSHA activity number 337433619.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of Veterans Affairs - LOS Angeles National Cemetery — free Get an email when a new federal OSHA severe-injury report for U.S. Department of Veterans Affairs - LOS Angeles National Cemetery is published. One employer, no account, unsubscribe in one click.
Site address
950 S. SEPULVEDA BLVD. ADMIN BLDG
City
LOS ANGELES
State
CA
ZIP
90049
Mailing
950 S. SEPULVEDA BLVD., LOS ANGELES, CA 90049
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
812220
Employees
7
Ownership type
D

10 citations on file for this inspection.

1910.37 A03

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 7, 2012
Abate by
Jan 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    Administrative building hallway near kitchen: On or about 06NOV12, 1110hrs, A large plastic  wheeled bin was stored in front of, and blocking access to, doors marked as the emergency exit discharge on the posted fire escape plans posted in the building.
Recent events (1)
  • — Z (S) $0

1910.157 C04

Serious Gravity 1 1 instance 2 exposed
Issued
Dec 7, 2012
Abate by
Jan 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(4): Portable fire extinguishers were not kept in their designated places when not being used:    Admin office: On or about 06NOV12, 1030hrs, A fire extinguisher was not kept in its designated place.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 7, 2012
Abate by
Jan 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    Admin office: On or about 06NOV12, 1030hrs, a power strip was used to provide 120VAC electrical service to another power strip.
Recent events (1)
  • — Z (S) $0

1910.303 B07 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Dec 7, 2012
Abate by
Jan 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(iv): There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:    Administrative building reception: On or about 06NOV12, 1120hrs, an employee was exposed to inadvertent contact with the exposed electrical conductors of a receptacle outlet; the plastic face plate was broken at the connection point, exposing the conductors inside.
Recent events (1)
  • — Z (S) $0

1910.303 B08 I

Serious Gravity 5 1 instance 4 exposed
Issued
Dec 7, 2012
Abate by
Jan 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(8)(i): Electric equipment was not firmly secured to the surface on which it was mounted:    Administrative building kitchen: On or about 06NOV12, 1055hrs, a circuit breaker panel was fastened to the kitchen wall with only two of the six available fastener points utilized, resulting in the panel being loose, and freely moving to the touch.
Recent events (1)
  • — Z (S) $0

1910.304 B03 I

Serious Gravity 5 2 instances 7 exposed
Issued
Dec 7, 2012
Abate by
Jan 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops did not have ground-fault circuit-interrupter protection for personnel:    (a) Administrative building mens room: On or about 06NOV12, 1045hrs, the ground fault circuit interrupter receptacle outlet installed in the restroom was not functional, failing to trip the circuit when tested.     (b) Administrative building womens room: On or about 06NOV12, 1048hrs, the ground fault circuit interrupter receptacle outlet installed in the restroom was not functional, failing to trip the circuit when tested exposing employees to electrical shock.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 7, 2012
Abate by
Jan 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure:    Admin office: On or about 06NOV12, 1030hrs, an extension cord providing 120VAC service to the office equipment was in use for over six months.
Recent events (1)
  • — Z (S) $0

1910.1200 E01

Serious Gravity 5 1 instance 7 exposed
Issued
Dec 7, 2012
Abate by
Jan 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:    At the facility: On or about 06NOV12, 1000hrs, The employer did not provide a hazardous communication program addressing labeling of hazardous chemicals, material safety data sheets, and training addressing the chemicals in the workplace.
Recent events (1)
  • — Z (S) $0

1960.58

Serious Gravity 5 1 instance 7 exposed
Issued
Dec 7, 2012
Abate by
Jan 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1960.58:  The Agency did not provide training for collateral duty safety and health personnel including all members of certified occupational safety and health committees commensurate with the scope of their assigned responsibilities:    At the facility: On or about 06NOV12, 1000hrs, The employer did not provide training for collateral safety and health personnel commensurate with the scope of the assigned responsibilities.
Recent events (1)
  • — Z (S) $0

1904.32 A

Other-than-serious 1 instance 7 exposed
Issued
Dec 7, 2012
Abate by
Jan 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1904.32(a): The employer did not ensure that at the end of the year an annual summary of injuries and illnesses on the OSHA 300 Log was created, certified and posted.     At the facility: On or about 06NOV12, 1000hrs, the employer failed to create and certify an annual summary of injuries and illnesses for the last five years. The employer did not maintain a log of recordable injuries and illnesses in order to create the annual summary.
Recent events (1)
  • — Z (O) $0

View U.S. Department of Veterans Affairs - LOS Angeles National Cemetery's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337433619.