WASHINGTON, PA —
OSHA Inspection: ENERSYS
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of ENERSYS in 80 STEWART AVENUE, WASHINGTON, PA 15301 (NAICS 335911). OSHA activity number 337552418.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ENERSYS
- Site address
- 80 STEWART AVENUE
- City
- WASHINGTON
- State
- PA
- ZIP
- 15301
- Mailing
- 80 STEWART AVENUE, WASHINGTON, PA 15301
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 335911
- Employees
- 30
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.106 D07 III
- Issued
- Feb 13, 2013
- Penalty
- Initial $3,000 · Current $2,250 Reduced
General-duty citation text
29 CFR 1910.106(d)(7)(iii): Open flames and smoking were permitted in flammable or combustible liquid storage areas: a) At the facility, on or about November 27, 2012 - An open flame coming from a stove top was in a flammable liquid storage area.
Recent events (2)
- — I (O) $2250
- — Z (S) $3000
1910.107 B05 I
- Issued
- Feb 13, 2013
- Penalty
- Initial $4,000 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.107(b)(5)(i): Visible gauges or audible alarms or pressure activated devices were not installed to indicate or insure that the required air velocity is maintained: a) At the facility, on or about November 27, 2012 - A dry type spray booth did not have a visible gauge, audible alarm, or pressure activated device installed to insure air velocity is maintained. Employees spray High Gloss Enamel White, Product #218-234-T, with a Graco AirPro spray gun and compressed air in the dry type spray booth.
Recent events (2)
- — I (S) $3000
- — Z (S) $4000
1910.107 B05 IV
- Issued
- Feb 13, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(b)(5)(iv): Space within the spray booth on the downstream and upstream sides of filters were not protected with approved automatic sprinklers: a) At the facility, on or about November 27, 2012 - The dry type spray booth did not have approved automatic sprinklers on the upstream side of filters. Employees spray High Gloss Enamel White, Product #218-234-T, with a Graco AirPro spray gun and compressed air in the dry type spray booth.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.107 B09
- Issued
- Feb 13, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(b)(9): A clear space of not less than 3 feet on all sides was not kept free from storage or combustible construction: a) At the facility, on or about November 27, 2012 - The dry type spray booth did not have a clear space of 3 feet on the left and right sides. Employees spray High Gloss Enamel White, Product #218-234-T, with a Graco AirPro spray gun and compressed air in the dry type spray booth.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.107 D05
- Issued
- Feb 13, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(d)(5): Electric motor(s) driving exhaust fan(s) for spray booth(s) were located inside the booth(s): a) At the facility, on or about November 27, 2012 - A Dayton Direct Drive Fan Motor, Model # 994207G, was located inside the dry type spray booth. The Dayton Direct Drive Fan Motor was driving a Dayton 20'' Med.-Duty Exhaust Fan, Model # 4C009F. Employees spray High Gloss Enamel White, Product #218-234-T, with a Graco AirPro spray gun and compressed air in the dry type spray booth.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 C02 II
- Issued
- Feb 13, 2013
- Abate by
- Apr 19, 2013
- Penalty
- Initial $3,000 · Current $2,250 Reduced
General-duty citation text
29 CFR 1910.134(c)(2)(ii): The employer did not establish and implement those elements of a written program necessary to ensure that any employee using a respirator voluntarily was medically able to use that respirator, and that the respirator was cleaned, stored, and maintained so that its use does not present a health hazard to the user: a) At the facility, on or about November 27, 2012 - A painter voluntarily wearing a North half-mask tight fitting respirator during spraying operations did not receive a medical evaluation. b) At the facility, on or about November 27, 2012 - A grinder voluntarily wearing a North half-mask tight fitting respirator while grinding did not receive a medical evaluation. c) At the facility, on or about November 27, 2012 - A welder voluntarily wearing a Miller LPR-100 half-mask tight fitting respirator while welding did not receive a medical evaluation.
Recent events (2)
- — I (O) $2250
- — Z (S) $3000
More inspections at Enersys
View Enersys's full OSHA safety record →
More inspections in this industry (NAICS 335911)
More inspections in PA
Source