Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PIKE COUNTY ENVIRONMENTAL, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PIKE COUNTY ENVIRONMENTAL, INC. in 1116 DELAWARE AVENUE, MATAMORAS, PA 18336 (NAICS 221320). OSHA activity number 337590012.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pike County Environmental, INC. — free Get an email when a new federal OSHA severe-injury report for Pike County Environmental, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1116 DELAWARE AVENUE
City
MATAMORAS
State
PA
ZIP
18336
Mailing
PO BOX 127, MATAMORAS, PA 18336
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221320
Employees
5
Ownership type
A

7 citations on file for this inspection.

1910.22 C

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 21, 2013
Abate by
Apr 25, 2013
Penalty
Initial $1,700 · Current $1,700
29 CFR 1910.22(c):     Covers and/or guardrails were not provided to protect personnel from the hazards of open pits, tanks, vats, ditches, etc.    a) Aeration lagoon - Employees perform a daily entrance into the lagoon area to stand or walk near the aeration lagoon to take water samples.  The lagoon 10-15 feet deep with a plastic liner and is not equipped with either a cover or guardrails, thereby exposing the employees to a drowning hazard, observed on or about 11-28-12.    b) Clarifier shed - An employee enters the building several times times a day and works near or on a traveling bridge above a tank containing 10-14 foot deep sewage.  The tank is not covered or guarded, thereby exposing the employee to a drowning hazard, on or about 11-28-12.       Abatement documentation required.
Recent events (1)
  • — Z (S) $1700

1910.23 C02

Serious Gravity 5 2 instances 2 exposed
Issued
Mar 21, 2013
Abate by
Apr 16, 2013
Penalty
Initial $1,700 · Current $1,700
29 CFR 1910.23(c)(2):     Runways four feet or more above floor or ground level were not guarded by standard railings (or the equivalent).      a) Dump Station  -  Employees unloading their vacuum trucks stood on runways where the railings were not complete. Railings were missing at  4'2" near the bar screen rake out and at 15 feet high near the barrel, thereby exposing the employees to a serious hazard, on or about 11-28-12.      Abatement certification required.
Recent events (1)
  • — Z (S) $1700

1910.23 D01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 21, 2013
Abate by
Apr 16, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.23(d)(1)(ii):     Stairway(s) less than 44 inches wide having one side open, did not have at least one stair railing on the open side:    a) Dump Station - Employees used a set of 17 step high fixed metal stairs to access between the upper and lower ground levels.  The stairs had no stair railing on the open side thereby exposing the employees to a serious hazard,  observed on or about 11-28-13.    Abatement certificatioin required.
Recent events (1)
  • — Z (S) $0

5(a)(1)

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 21, 2013
Abate by
Apr 2, 2013
Penalty
Initial $1,360 · Current $1,360
OSH ACT of 1970 Section (5)(a)(1):     Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing for likely to cause death or serious physical harm to employees in that employees were exposed to a caught in hazard from the manually controlled fixed conveyors.    a) Employees operate a 2.5 meter Phoenix Belt Press to remove water from sewage sludge.  The conveyor was not equipped with an operable emergency stop cord, thereby exposing the employee to a serious hazard, observed on or about 11-21-13.     Among other methods, one feasible and acceptable means to correct these hazards is to comply with the requirements outlined in the NFPA 79 10.7.1.1 Electrical Standard for Industrial Machinery.     Abatement certification required.
Recent events (1)
  • — Z (S) $1360

1910.212 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 21, 2013
Abate by
Apr 16, 2013
Penalty
Initial $1,360 · Current $1,360
29 CFR 1910.212(a)(1):     One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by ingoing nip points and rotating parts :    a) Employees operate a 2.5 meter Phoenix Belt Press to remove water from sewage sludge.  The conveyor had an area where the belt crossed a roller that was unguarded thereby exposing the employee to a hazard, on or about 11-21-13.     Abatement certificationn required.
Recent events (1)
  • — Z (S) $1360

1910.305 B01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 21, 2013
Abate by
Apr 2, 2013
Penalty
Initial $1,360 · Current $1,360
29 CFR 1910.305(b)(1)(ii):     Unused openings in boxes, cabinets, or fittings were not effectively closed:    (a) Mechanics Garage - An employee used an outlet box as part of a flexible wiring circuit and the box had a missing knockout on the back of the box, thereby exposing the employee to a serious hazard, observed on or about 11-28-13.    Abatement certification required.
Recent events (1)
  • — Z (S) $1360

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 21, 2013
Abate by
Apr 2, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):     Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    (a) Garage - A knockout type of electrical junction box, being used as a receptacle box, was not used in accordance with its listing and labeling instructions (by a nationally recognized testng laboratory) as the junction box was improperly attached to a flexible cord instead of being secured to a structure.  The cord box assembly supplied power to a work light thereby exposing the employee to a shock hazard, observed on or about 11-28-12.    Abatement certification required
Recent events (1)
  • — Z (S) $0

View Pike County Environmental, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337590012.