Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TWIN BROTHERS MARINE, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of TWIN BROTHERS MARINE, LLC in 322 TWIN BROTHERS ROAD, FRANKLIN, LA 70538 (NAICS 336611). OSHA activity number 337622849.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Twin Brothers Marine, LLC — free Get an email when a new federal OSHA severe-injury report for Twin Brothers Marine, LLC is published. One employer, no account, unsubscribe in one click.
Site address
322 TWIN BROTHERS ROAD
City
FRANKLIN
State
LA
ZIP
70538
Mailing
P.O. BOX 2426, MORGAN CITY, LA 70381
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336611
Employees
150
Ownership type
A

3 citations on file for this inspection.

1910.304 B03 II C 3

Serious Gravity 5 1 instance 3 exposed
Issued
Mar 8, 2013
Abate by
Mar 23, 2013
Penalty
Initial $4,500 · Current $4,300 Reduced
29 CFR 1910.304(b)(3)(ii)(C)(3):     Each cord set, attachment cap, plug, and receptacle of cord sets, and any equipment connected by cord and plug, except cord sets and receptacles which are fixed and not exposed to damage, shall be visually inspected before each day's use for external defects, such as deformed or missing pins or insulation damage, and for indications of possible internal damage. Equipment found damaged or defective shall not be used until repaired;    a)	On or about November 29, 2012; at the BP Yard area of the facility, the employer allowed employees to work near a welding machine and two temporary power distribution panels, which were connected by cord and plug and were not visually inspected before each days use for external defects.
Recent events (3)
  • — C (S) $4500
  • — F (S) $4300
  • — Z (S) $4500

1910.305 G02 III

Serious Gravity 5 3 instances 2 exposed
Issued
Mar 8, 2013
Abate by
Mar 23, 2013
Penalty
Initial $4,500 · Current $0 Reduced
29 CFR 1910.305(g)(2)(iii):     Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.    a)	On or about November 29, 2012; on the east side of the BP Yard area, the employer allowed employees to use the Idealarc AC/DC 250 (S/N-U1051208351) welding machine to weld pipe together.  The welding machine electrical cord did not have adequate strain relief.        b)	On or about November 29, 2012; on the east side of the BP Yard area, the employer allowed employees to use a distribution transformer (S/N-J05M10023) which had an electrical cord that was not provided adequate strain relief.  The distribution transformer is part of a temporary power distribution panel that is used by employees to power portable grinders.      c)	On or about November 29, 2012; at the center of the BP Yard area, the employer allowed employees to use a distribution transformer, which had an electrical cord that was not provided adequate strain relief.  The distribution transformer is part of a temporary power distribution panel that is used by employees to power portable grinders.
Recent events (3)
  • — C (S) $4500
  • — F (S) $0
  • — Z (S) $4500

1910.305 B01 I

Other-than-serious 1 instance 2 exposed
Issued
Mar 8, 2013
Abate by
Mar 23, 2013
Penalty
Initial $4,500 · Current $2,700 Reduced
29 CFR 1910.305(b)(1)(i):     Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed.    a)	On or about November 29, 2012; on the east side of the BP Yard area, the employer allowed employees to work near a Square D safety switch that had a conductor entering the cutout box which was not protected from abrasion, and an the opening through which the conductor entered was not effectively closed.
Recent events (3)
  • — C (S) $4500
  • — F (O) $2700
  • — Z (S) $4500

View Twin Brothers Marine, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337622849.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.