FRANKLIN, LA —
OSHA Inspection: TWIN BROTHERS MARINE, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of TWIN BROTHERS MARINE, LLC in 322 TWIN BROTHERS ROAD, FRANKLIN, LA 70538 (NAICS 336611). OSHA activity number 337622849.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TWIN BROTHERS MARINE, LLC
- Site address
- 322 TWIN BROTHERS ROAD
- City
- FRANKLIN
- State
- LA
- ZIP
- 70538
- Mailing
- P.O. BOX 2426, MORGAN CITY, LA 70381
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336611
- Employees
- 150
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.304 B03 II C 3
- Issued
- Mar 8, 2013
- Abate by
- Mar 23, 2013
- Penalty
- Initial $4,500 · Current $4,300 Reduced
General-duty citation text
29 CFR 1910.304(b)(3)(ii)(C)(3): Each cord set, attachment cap, plug, and receptacle of cord sets, and any equipment connected by cord and plug, except cord sets and receptacles which are fixed and not exposed to damage, shall be visually inspected before each day's use for external defects, such as deformed or missing pins or insulation damage, and for indications of possible internal damage. Equipment found damaged or defective shall not be used until repaired; a) On or about November 29, 2012; at the BP Yard area of the facility, the employer allowed employees to work near a welding machine and two temporary power distribution panels, which were connected by cord and plug and were not visually inspected before each days use for external defects.
Recent events (3)
- — C (S) $4500
- — F (S) $4300
- — Z (S) $4500
1910.305 G02 III
- Issued
- Mar 8, 2013
- Abate by
- Mar 23, 2013
- Penalty
- Initial $4,500 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws. a) On or about November 29, 2012; on the east side of the BP Yard area, the employer allowed employees to use the Idealarc AC/DC 250 (S/N-U1051208351) welding machine to weld pipe together. The welding machine electrical cord did not have adequate strain relief. b) On or about November 29, 2012; on the east side of the BP Yard area, the employer allowed employees to use a distribution transformer (S/N-J05M10023) which had an electrical cord that was not provided adequate strain relief. The distribution transformer is part of a temporary power distribution panel that is used by employees to power portable grinders. c) On or about November 29, 2012; at the center of the BP Yard area, the employer allowed employees to use a distribution transformer, which had an electrical cord that was not provided adequate strain relief. The distribution transformer is part of a temporary power distribution panel that is used by employees to power portable grinders.
Recent events (3)
- — C (S) $4500
- — F (S) $0
- — Z (S) $4500
1910.305 B01 I
- Issued
- Mar 8, 2013
- Abate by
- Mar 23, 2013
- Penalty
- Initial $4,500 · Current $2,700 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. a) On or about November 29, 2012; on the east side of the BP Yard area, the employer allowed employees to work near a Square D safety switch that had a conductor entering the cutout box which was not protected from abrasion, and an the opening through which the conductor entered was not effectively closed.
Recent events (3)
- — C (S) $4500
- — F (O) $2700
- — Z (S) $4500
More inspections at Twin Brothers Marine, LLC
View Twin Brothers Marine, LLC's full OSHA safety record →
More inspections in this industry (NAICS 336611)
More inspections in LA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337622849.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.