BUFFALO, NY —
OSHA Inspection: INNOVISION LED
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of INNOVISION LED in 979 NORTHAMPTON STREET, BUFFALO, NY 14211 (NAICS 339950). OSHA activity number 337675821.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INNOVISION LED
- Site address
- 979 NORTHAMPTON STREET
- City
- BUFFALO
- State
- NY
- ZIP
- 14211
- Mailing
- 979 NORTHAMPTON STREET, BUFFALO, NY 14211
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 339950
- Employees
- 12
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.24 H
- Issued
- Feb 4, 2013
- Abate by
- Mar 1, 2013
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.24(h): Standard railings were not provided on the open sides of all exposed stairways and stair platforms: a) On or about 12/11/2012 in the assembly area - where there was no railing on the open side of the stairway to the upstairs assembly area. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
1910.36 D01
- Issued
- Feb 4, 2013
- Abate by
- Mar 1, 2013
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.36(d)(1): A required exit(s), way of approach thereto, and/or way of travel from the exit into the street or open space, was not continuously maintained free of all obstructions or impediments to full instant use in the case of fire or other emergency: a) On or about 12/11/2012 in the metal fabrication room; where the exit door was locked in the closed position with three sliding bolt locks (top, middle and bottom). ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
1910.106 E02 IV A
- Issued
- Feb 4, 2013
- Abate by
- Mar 1, 2013
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.106(e)(2)(iv)(a): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 F (37.8 C), were not kept in covered containers when not actually in use: a) On or about 12/11/2012 in the paint room - where there was an open, uncovered 5 gallon pail of solvent. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
1910.107 C06
- Issued
- Feb 4, 2013
- Abate by
- Mar 1, 2013
- Penalty
- Initial $2,800 · Current $0 Reduced
General-duty citation text
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: a) On or about 12/11/2012 in the paint room - where standard duty electrical equipment including, but not limited to: switches, lighting and motors, was installed in the area where spray finishing of flammable coatings was performed. ABATEMENT DOCUMENTATION REQUIRED
Recent events (2)
- — I (O) $0
- — Z (S) $2800
1910.212 A03 II
- Issued
- Feb 4, 2013
- Abate by
- Mar 1, 2013
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s): a) On or about 12/11/2012 in the fabrication area - where the table saw used for cutting metal and plastic was not provided with a guard for the saw blade. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
1910.303 B02
- Issued
- Feb 4, 2013
- Abate by
- Mar 1, 2013
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) On or about 12/11/2012 in the metal fabrication room - where a metal duplex receptacle box at the end of a flexible cord was used as an extension cord. The metal box was not securely mounted as required by the National Electrical Code. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
1910.303 G02 I
- Issued
- Feb 4, 2013
- Abate by
- Mar 1, 2013
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) On or about 12/11/2012 in the router operations room - where the electrical panel for the heater and receptacles was missing the front cover, exposing employees to "live" electrical parts. ABATEMENT CERTIFICATION REQUIRED