LEECHBURG, PA —
OSHA Inspection: ATI ALLEGHENY LUDLUM BAGDAD
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ATI ALLEGHENY LUDLUM BAGDAD in 585 SILICON DRIVE, LEECHBURG, PA 15656 (NAICS 331111). OSHA activity number 337778617.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ATI ALLEGHENY LUDLUM BAGDAD
- Site address
- 585 SILICON DRIVE
- City
- LEECHBURG
- State
- PA
- ZIP
- 15656
- Mailing
- 585 SILICON DRIVE, LEECHBURG, PA 15656
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 331111
- Employees
- 250
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 B06
- Issued
- Mar 12, 2013
- Penalty
- Initial $3,740 · Current $3,740
General-duty citation text
29 CFR 1910.303(b)(6): No conductors or equipment can be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures unless identified for the operating environment: (a) Facility, Building Column 70: On or before December 10, 2012, employees were exposed to burn hazards from arcing parts in that rain water was leaking onto energized wiring.
Recent events (2)
- — I (O) $3740
- — Z (S) $3740
1910.303 B07 IV
- Issued
- Mar 12, 2013
- Abate by
- Sep 2, 2013
- Penalty
- Initial $4,675 · Current $4,675
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating were used: (a) Facility, On or about October 3, 2012, employees were exposed to electrical hazards from broken switches and a missing switch handle. (b) Facility, Number 35 Slitter MCC Gear, Switch 9: On or about October 3, 2012, employees were exposed to live electrical parts of 480 Volts AC 3 Phase when a switch broke and was missing requiring the door to be opened to achieve energy isolation. (c) Facility, Number 35 Slitter MCC Gear, Switch 5: On or about October 3, 2012, employees were exposed to live electrical parts of 480 Volts AC 3 Phase when a switch broke and was missing requiring the door to be opened to achieve energy isolation. (d) Facility, Doghouse 3-5, Number 4 Tunnel Furnace Zone 4 and 5: On or before December 10, 2012, the employer did not replace a broken switch to isolate zones 4 and 5. (e) Facility, Crane Disconnect, Hot Rail Columns 51 to 66: On or before December 10, 2012, employees were exposed to fire and/or arcing part hazards when a disconnect switch was not fully engaged. (f) Facility, Number 3 Tunnel Furnace, Zone 1: On or before December 10, 2012, the employer did not replace a broken switch to isolate zone 1. (g) Facility, Number 3 Tunnel Furnace, Zone 2: On or before December 10, 2012, the employer did not replace a broken switch to isolate zone 2. (h) Facility, Number 3 Tunnel Furnace, Zone 4 and : On or before December 10, 2012, the employer did not replace a broken switch to isolate zone 4 and 5. (i) Facility, Number 3 Tunnel Furnace, Zone 6: On or before December 10, 2012, the employer did not replace a broken switch to isolate zone 6. (j) Facility, Number 3 Tunnel Furnace, Zone 7: On or before December 10, 2012, the employer did not replace a broken switch to isolate zone 7. (k) Facility, Number 3 Tunnel Furnace, Zone 8: On or before December 10, 2012, the employer did not replace a broken switch to isolate zone 8. (l) Facility, Number 3 Tunnel Furnace, Zone 1 Feed: On or before December 10, 2012, the employer did not replace/install a missing switch handle.
Recent events (2)
- — I (S) $4675
- — Z (S) $4675
1910.304 F01 VI
- Issued
- Mar 12, 2013
- Abate by
- Apr 26, 2013
- Penalty
- Initial $4,675 · Current $0 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(vi): Circuit breakers did not clearly indicate whether they are in the open (off) or closed (on) position: (a) Facility, Number 35 Slitter MCC Gear, Switch 10: On or about October 3, 2012, the employer did not ensure a switch was installed to open or close the circuit. (b) Facility, Number 35 Slitter MCC Gear, Switch 9: On or about October 3, 2012, the employer did not ensure a switch was installed to open or close the circuit. (c) Facility, Number 35 Slitter MCC Gear, Switch 5: On or about October 3, 2012, the employer did not ensure a switch was installed to open or close the circuit. (d) Facility, Doghouse 3-5, Number 4 Tunnel Furnace Zone 4 and 5: On or before December 10, 2012, the employer did not ensure a switch was installed to open or close the circuit. (e) Facility, Number 3 Tunnel Furnace, Zone 1: On or before December 10, 2012, the employer did not ensure a switch was installed to open or close the circuit. (f) Facility, Number 3 Tunnel Furnace, Zone 2: On or before December 10, 2012, the employer did not ensure a switch was installed to open or close the circuit. (g) Facility, Number 3 Tunnel Furnace, Zone 4 and 5: On or before December 10, 2012, the employer did not ensure a switch was installed to open or close the circuit. (h) Facility, Number 3 Tunnel Furnace, Zone 6: On or before December 10, 2012, the employer did not ensure a switch was installed to open or close the circuit. (i) Facility, Number 3 Tunnel Furnace, Zone 7: On or before December 10, 2012, the employer did not ensure a switch was installed to open or close the circuit. (j) Facility, Number 3 Tunnel Furnace, Zone 8: On or before December 10, 2012, the employer did not ensure a switch was installed to open or close the circuit.
Recent events (2)
- — I (S) $0
- — Z (S) $4675
1910.303 G02 I
- Issued
- Mar 12, 2013
- Abate by
- Mar 22, 2013
- Penalty
- Initial $3,740 · Current $3,740
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): (a) Facility, Doghouse 3-5, Bottom Box: On or about November 19, 2012, employees were exposed to live electrical parts powered at 120 Volts AC when a cover was missing on a Femco box. (b) Facility, Doghouse 3-5, Top Box: On or about November 19, 2012, employees were exposed to live electrical parts powered at 120 Volts AC when a cover was missing on a Femco box. (c) Facility, Doghouse 6-9, Bottom Box: On or about November 19, 2012, employees were exposed to live electrical parts powered at 120 Volts AC when a cover was missing on a Femco box. (d) Facility, Doghouse 6-9, Top Box: On or about November 19, 2012, employees were exposed to live electrical parts powered at 120 Volts AC when a cover was missing on a Femco box. (e) Facility, Doghouse 1-3, Top Box: On or about November 19, 2012, employees were exposed to live electrical parts powered at 120 Volts AC when a cover was missing on a Femco box. (f) Facility, Doghouse 1-3, Raceway: On or about November 19, 2012, a cover was not secured along the bottom of the pull box creating a gap of approximately one inch. (g) Facility, Solenoid Cabinet: On or about November 19, 2012, employees were exposed to live electrical parts powered at 120 Volts AC when a cover was hinged in the open position. (h) Facility, Number 35 MCC Gear, Number Five Welder AC Disconnect: On or about October 3, 2012, employees were exposed to live electrical parts of 480 Volts AC 3 Phase when a switch was missing creating a hole in the cabinet door.
Recent events (2)
- — I (S) $3740
- — Z (S) $3740
1910.303 B08 I
- Issued
- Mar 12, 2013
- Penalty
- Initial $3,740 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(8)(i): Electric equipment was not firmly secured to the surface on which it is mounted: (a) Facility, Solenoid Cabinet: On or about November 19, 2012, employees were exposed to arcing parts in that fuse holders were not secured to the cabinet.
Recent events (2)
- — I (S) $0
- — Z (S) $3740
1910.1200 F06
- Issued
- Mar 12, 2013
- Abate by
- Apr 26, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(6): The employer used written materials, such as signs, placards, process sheets, or batch tickets in lieu of affixing labels to individual stationary process containers that failed to identify the container(s) to which they were applicable and did not convey the information required by 29 CFR 1910.1200(f)(5): (a) Facility, Process Piping: On or before December 10, 2012, process piping used for containing and delivering nitrogen was painted orange with a red stripe which contradicts the "Bagdad Plant Piping Color Codes".
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at ATI Allegheny Ludlum Bagdad
View ATI Allegheny Ludlum Bagdad's full OSHA safety record →
More inspections in this industry (NAICS 331111)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 337778617.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.