OSHA Inspection: AMERIGLOBE FIBC SOLUTIONS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AMERIGLOBE FIBC SOLUTIONS in 153 S. LONG ST., LAFAYETTE, LA 70506 (NAICS 326111). OSHA activity number 337829816.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ameriglobe Fibc Solutions — free Get an email when a new federal OSHA severe-injury report for Ameriglobe Fibc Solutions is published. One employer, no account, unsubscribe in one click.
Site address
153 S. LONG ST.
City
LAFAYETTE
State
LA
ZIP
70506
Mailing
153 S. LONG ST., LAFAYETTE, LA 70506
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326111
Employees
35
Ownership type
A

5 citations on file for this inspection.

1910.147 C04 I

Serious Gravity 5 5 instances 2 exposed
Issued
Jan 25, 2013
Abate by
Mar 1, 2013
Penalty
Initial $3,500 · Current $2,100 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed and documented for the control of potentially hazardous energy when employees were engaged in activities covered by this section.  The procedures shall clearly and specifically outline the means to enforce compliance including, but not limited to, the following:      The employer did not develop written procedures with specific steps for the control of potentially hazardous energy regarding machines and equipment such as, but not limited to:    a) Bay 1: Two bag press machines    b) Bay 2:        1. Bag press machine        2. Scrap baler machine        3. Manual cutting machine    c) Bay 3: Bag filling station
Recent events (2)
  • — I (S) $2100
  • — Z (S) $3500

1910.179 J03

Serious Gravity 1 6 instances 2 exposed
Issued
Jan 25, 2013
Abate by
Mar 1, 2013
Penalty
Initial $2,100 · Current $1,260 Reduced
29 CFR 1910.179(j)(3): Periodic inspection. Complete inspections of the crane shall be performed at intervals as generally defined in paragraph (j)(1)(ii)(b) of this section, depending upon its activity, severity of service, and environment, or as specifically indicated below. These inspections shall include the requirements of paragraph (j)(2) of this section and in addition, the following items. Any deficiencies such as listed shall be carefully examined and determination made as to whether they constitute a safety hazard:      The employer failed to ensure that overhead gantry cranes throughout the facility were periodically inspected:      1. Bay 1 - Two overhead gantry cranes      2. Bay 2 - One overhead gantry crane (Double compression unit)      3. Bay 3 - Two overhead gantry cranes      4. Bay 4 - One overhead gantry crane
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.305 B01 II

Serious Gravity 1 1 instance 3 exposed
Issued
Jan 25, 2013
Abate by
Feb 20, 2013
Penalty
Initial $2,100 · Current $1,260 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed.      a) Bay 4, Panel K; an electrical panel did not have a blank or knockout to cover a circuit breaker opening, exposing employees to possible contact with live electrical conductors and the hazard of an electrical shock.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.305 B02 I

Serious Gravity 5 3 instances 5 exposed
Issued
Jan 25, 2013
Abate by
Feb 13, 2013
Penalty
Initial $3,500 · Current $2,100 Reduced
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear.      a) Wash Room; An electrical box did not have a cover. The wires inside the box were exposed and live.     b) Packing department:       1. Glue Machine; an electrical box on front of the machine was missing the cover. The box had tape over the wires inside                which were live.        2. Ventilator machine; faceplate of the wall switch was missing.     This condition exposed employees to an electric shock hazard.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $3500

1910.303 F02

Other-than-serious 1 instance 2 exposed
Issued
Jan 25, 2013
Abate by
Feb 6, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident.      a) Bay 1; electrical circuits in panel FPE were not labeled for its intended use.