BRIDGEVILLE, PA —
OSHA Inspection: D & S INDUSTRIAL CONTRACTING INC.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of D & S INDUSTRIAL CONTRACTING INC. in 600 MAYER STREET, BRIDGEVILLE, PA 15017 (NAICS 811310). OSHA activity number 338093818.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- D & S INDUSTRIAL CONTRACTING INC.
- Site address
- 600 MAYER STREET
- City
- BRIDGEVILLE
- State
- PA
- ZIP
- 15017
- Mailing
- 3100 CASTEEL DRIVE, CORAOPOLIS, PA 15108
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811310
- Employees
- 31
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.252 A02 II
- Issued
- Jan 22, 2013
- Penalty
- Initial $2,380 · Current $1,580 Reduced
General-duty citation text
29 CFR 1910.252(a)(2)(ii): Suitable extinguishing equipment was not maintained in a state of readiness for instant use: (a) Universal Stainless Facility, Creek Building, Bridgeville, PA: On or about 01/02/13 an Ansul Sentry 5 pound dry chemical fire extinguisher assigned for use to the fire watcher was reading "Recharge" and was not in a state of readiness for instant use should a fire occur.
Recent events (2)
- — I (S) $1580
- — Z (S) $2380
1910.252 A02 III A 1
- Issued
- Jan 22, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.252(a)(2)(iii)(A)(1): The employer did not provide fire watchers whenever welding or cutting was performed, where appreciable combustible material in building construction or contents was closer than 35 feet (10.7 m) to the point of operation: (a) Universal Stainless Facility, Creek Building, Bridgeville, PA: On or about 12/19/12 a fire watcher was not provided when cutting operations were conducted approximately 18 feet above the plate leveler. A fire occurred when a spark or hot material fell onto the unprotected hydraulic hoses lying on the floor. The fire was extinguished by an employee with the use of a fire extinguisher obtained from one of the host employer's fork trucks that was parked in the area.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.252 A02 VII
- Issued
- Jan 22, 2013
- Penalty
- Initial $2,380 · Current $1,580 Reduced
General-duty citation text
29 CFR 1910.252(a)(2)(vii): Where relocation of combustible was impracticable, cutting or welding was permitted when combustibles were not protected with flame proofed covers or otherwise shielded with metal, asbestos guards, or curtains: (a) Universal Stainless Facility, Creek Building, Bridgeville, PA: On or about 12/19/12 cutting operations were conducted above the plate leveler and the hydraulic hoses for the machine, which were not relocatable, were not protected by flame proof covers or shielded with metal, asbestos guards, or curtains. A fire occurred when sparks and/or hot, cut material(s) fell onto uncovered hydraulic hoses lying on the floor below the work area.
Recent events (2)
- — I (S) $1580
- — Z (S) $2380
1910.252 A02 XIV B
- Issued
- Jan 22, 2013
- Penalty
- Initial $2,380 · Current $1,580 Reduced
General-duty citation text
29 CFR 1910.252(a)(2)(xiv)(B): The supervisor did not determine the combustible materials and hazardous areas present or likely to be present in the work location: (a) Universal Stainless Facility, Creek Building, Bridgeville, PA: On or about 12/19/12 cutting operations were being conducted over the plate leveler and a fire occurred when sparks and/or hot material fell onto the machine's hydraulic hoses lying on the floor below. The supervisor had not check the work area to determine if combustible materials or any other hazards were present prior to the start of the work.
Recent events (2)
- — I (S) $1580
- — Z (S) $2380
1910.252 A02 XIV F
- Issued
- Jan 22, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.252(a)(2)(xiv)(F): The supervisor did not determine that fire protection and extinguishing equipment are properly located at the site: (a) Universal Stainless Facility, Creek Building, Bridgeville, PA: On or about 12/19/12 cutting operations were being conducted over the plate leveler and a fire occurred when sparks and/or hot material fell onto the machine's hydraulic hoses lying on the floor below. The cutting operations had been conducted without having fire extinguishing equipment readily available for use. The supervisor utilized fire extinguishing equipment found on the host employer's fork truck that was parked in the area to extinguish the fire.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 811310)