OSHA Inspection: S.M. FOX CONSTRUCTION INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of S.M. FOX CONSTRUCTION INC. in 3900 BROADWAY AVE., SHEFFIELD VILLAGE, OH 44035 (NAICS 236115). OSHA activity number 338150816.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch S.M. FOX Construction INC. — free Get an email when a new federal OSHA severe-injury report for S.M. FOX Construction INC. is published. One employer, no account, unsubscribe in one click.
Site address
3900 BROADWAY AVE.
City
SHEFFIELD VILLAGE
State
OH
ZIP
44035
Mailing
9632 PATRICIA CT., ELYRIA, OH 44035
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236115
Employees
6
Ownership type
A

8 citations on file for this inspection.

1926.100 A

Serious Gravity 5 1 instance 6 exposed
Issued
Apr 11, 2013
Abate by
Apr 23, 2013
Penalty
Initial $1,600 · Current $960 Reduced
29 CFR 1926.100(a): Employees working in areas where there was a possible danger of head injury from impact, or falling or flying objects, or from electrical shock and burns, were not protected by protective helmets:          On and before 12/14/2012, during the renovation of a commercial property, an employee without head protection was exposed to a potential head injury from falling powered tools and/or other supplies that were located on the upper level of the ladder scaffold.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1926.403 B02

Serious Gravity 5 3 instances 6 exposed
Issued
Apr 11, 2013
Penalty
Initial $1,600 · Current $960 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    The 3 metal junction boxes, attached to the main distribution panel located inside the crematorium, were not installed in a neat workmanlike manner.  The boxes were not mounted to a fixed surface nor connected to the conduit.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1926.404 B01 III C

Serious Gravity 5 1 instance 6 exposed
Issued
Apr 11, 2013
Abate by
Apr 23, 2013
Penalty
Initial $1,600 · Current $960 Reduced
29 CFR 1926.404(b)(1)(iii)(C): Where an assured equipment grounding conductor program was being utilized, the employer did not ensure that each cord set, attachment cap, plug and receptacle of cord sets, and any equipment connected by cord and plug, except cord sets and receptacles which are fixed and not exposed to damage, were not visually inspected fofore each day's use for external defects, such as deformed or missing pins or insulation damage, and for indicationsof possible internal damage:        As of 12/14/2012, the grounding prong/pin of the company's chop saw was missing.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1926.405 B01

Serious Gravity 5 1 instance 6 exposed
Issued
Apr 11, 2013
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed:    The unused openings in the cabinet were not effectively closed. The panelboard of the 208-240 volt/3 phase distribution cabinet had breaker openings that were closed insufficiently by electrical tape.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

1926.405 D

Serious Gravity 5 1 instance 6 exposed
Issued
Apr 11, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front:    On or about 12/14/2012, the employer did not ensure that the front panel of a 208-240 volt/3 phase distribution cabinet was replaced at the completion of electrical up grades.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.451 B01 II

Serious Gravity 10 1 instance 6 exposed
Issued
Apr 11, 2013
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1926.451(b)(1)(ii): The platform was not planked or decked as fully as possible and the remaining open space between the platform and the uprights exceeded 9.5 inches (24.1 cm):           On or about 12/14/2012, employees installing fascia boarding were using framed tubular steel scaffolding that was not fully planked.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

1926.451 E01

Serious Gravity 5 1 instance 6 exposed
Issued
Apr 11, 2013
Abate by
Apr 30, 2013
Penalty
Initial $2,400 · Current $1,920 Reduced
29 CFR 1926.451(e)(1): When scaffold platforms were more than 2 feet (0.6 m) above or below a point of access, portable ladders, hook-on ladders, attachable ladders, stair towers (scaffold stairways/towers), stairway-type ladders (such as ladder stands), ramps, walkways, integral prefabricated scaffold access, or direct access from other scaffold, structure, personnel hoist, or similar surface was not used.          On or about 12/14/2012 ladder scaffolding used by employees did not have a means of access.
Recent events (2)
  • — I (S) $1920
  • — Z (S) $2400

1926.451 F03

Serious Gravity 10 1 instance 6 exposed
Issued
Apr 11, 2013
Penalty
Initial $2,800 · Current $0 Reduced
29 CFR 1926.451(f)(3): Scaffolds and scaffold components were not inspected for visible defects by a competent person before each work shift, and after any occurrence which could affect a scaffold's structural integrity:      As of 12/14/2012, the framed tubular steel scaffolding was not inspected for defects before being placed into service.  The framed tubular steel scaffolding, used by employees installing fascia boards and/or completing roofing activities was not leveled and/or supported by a base plate.