Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DELFT BLUE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DELFT BLUE in 36A GARDEN ST., NEW YORK MILLS, NY 13417 (NAICS 311612). OSHA activity number 338259823.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Delft Blue — free Get an email when a new federal OSHA severe-injury report for Delft Blue is published. One employer, no account, unsubscribe in one click.
Establishment
DELFT BLUE
Site address
36A GARDEN ST.
City
NEW YORK MILLS
State
NY
ZIP
13417
Mailing
36A GARDEN ST., NEW YORK MILLS, NY 13417
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311612
Employees
58
Ownership type
A

7 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 3 instances 6 exposed
Issued
Jan 29, 2013
Abate by
Feb 25, 2013
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    a) On or about 1/15/2013, In the processing room:  Three meat transferring conveyors had unguarded pinch points.    Abatement certification is required for these items.
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.212 A05

Serious Gravity 5 6 exposed
Issued
Jan 29, 2013
Abate by
Feb 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(5): Fan blade guard(s) were not provided where the periphery of the blades was less than seven feet from the floor or working level:    a) On or about 1/15/2013, In the Compressor/Chemical room:  Air handlers had unguarded fan blades.    Abatement certification is required for these items.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 G05

Serious Gravity 5 6 exposed
Issued
Jan 29, 2013
Abate by
Feb 25, 2013
Penalty
Initial $3,500 · Current $2,450 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    a) On or about 1/15/2013, In the processing room: Metal cased scale was not provided with a path to ground.     Abatement certification is required for these items.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $3500

1910.305 E01

Serious Gravity 5 6 exposed
Issued
Jan 29, 2013
Abate by
Feb 25, 2013
Penalty
Initial $3,500 · Current $2,450 Reduced
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:    a) On or about 1/15/2013, In the processing room: Electrical panel was in use that was not rated for a damp or wet location.     Abatement certification is required for these items.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $3500

1910.305 J02 IV

Serious Gravity 5 1 exposed
Issued
Jan 29, 2013
Abate by
Feb 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:    a) On or about 1/15/2013, In the processing room: Electrical receptacle boxes not rated for wet or damp location were in used.     Abatement certification is required for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.132 D02

Other-than-serious 6 exposed
Issued
Jan 29, 2013
Abate by
Feb 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated, the person certifying that the evaluation has been performed, the date(s) of the hazard assessment, and, which identifies the document as a certification of hazard assessment:    a) On or about 1/15/2013, Throughout the facility: The employer had not verified that the required workplace hazard assessment has been performed through a written certification to determine if hazards are present. Employees may be exposed to eye and skin contact with corrosives materials.     Abatement certification is required for these items.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 2 instances 6 exposed
Issued
Jan 29, 2013
Abate by
Feb 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    a) On or about 1/15/2013, In the electric room:  Extension cords were being used in place of permanent wiring to power equipment.    b) On or about 1/15/2013, In the processing Area:  Extension cords were being used in place of permanent wiring to power equipment.    Abatement certification is required for these items.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Delft Blue's full OSHA safety record →