NEW YORK MILLS, NY —
OSHA Inspection: DELFT BLUE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DELFT BLUE in 36A GARDEN ST., NEW YORK MILLS, NY 13417 (NAICS 311612). OSHA activity number 338259823.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DELFT BLUE
- Site address
- 36A GARDEN ST.
- City
- NEW YORK MILLS
- State
- NY
- ZIP
- 13417
- Mailing
- 36A GARDEN ST., NEW YORK MILLS, NY 13417
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311612
- Employees
- 58
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.212 A01
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $2,800 · Current $1,960 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: a) On or about 1/15/2013, In the processing room: Three meat transferring conveyors had unguarded pinch points. Abatement certification is required for these items.
Recent events (2)
- — I (S) $1960
- — Z (S) $2800
1910.212 A05
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(5): Fan blade guard(s) were not provided where the periphery of the blades was less than seven feet from the floor or working level: a) On or about 1/15/2013, In the Compressor/Chemical room: Air handlers had unguarded fan blades. Abatement certification is required for these items.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 G05
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $3,500 · Current $2,450 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) On or about 1/15/2013, In the processing room: Metal cased scale was not provided with a path to ground. Abatement certification is required for these items.
Recent events (2)
- — I (S) $2450
- — Z (S) $3500
1910.305 E01
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $3,500 · Current $2,450 Reduced
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: a) On or about 1/15/2013, In the processing room: Electrical panel was in use that was not rated for a damp or wet location. Abatement certification is required for these items.
Recent events (2)
- — I (S) $2450
- — Z (S) $3500
1910.305 J02 IV
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: a) On or about 1/15/2013, In the processing room: Electrical receptacle boxes not rated for wet or damp location were in used. Abatement certification is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.132 D02
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated, the person certifying that the evaluation has been performed, the date(s) of the hazard assessment, and, which identifies the document as a certification of hazard assessment: a) On or about 1/15/2013, Throughout the facility: The employer had not verified that the required workplace hazard assessment has been performed through a written certification to determine if hazards are present. Employees may be exposed to eye and skin contact with corrosives materials. Abatement certification is required for these items.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G01 IV A
- Issued
- Jan 29, 2013
- Abate by
- Feb 25, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) On or about 1/15/2013, In the electric room: Extension cords were being used in place of permanent wiring to power equipment. b) On or about 1/15/2013, In the processing Area: Extension cords were being used in place of permanent wiring to power equipment. Abatement certification is required for these items.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Delft Blue
View Delft Blue's full OSHA safety record →
More inspections in this industry (NAICS 311612)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338259823.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.