SYRACUSE, NY —
OSHA Inspection: SOUTHERN WINE & SPIRITS OF UPSTATE NEW YORK INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of SOUTHERN WINE & SPIRITS OF UPSTATE NEW YORK INC. in 3063 COURT STREET, SYRACUSE, NY 13208 (NAICS 424820). OSHA activity number 338291412.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SOUTHERN WINE & SPIRITS OF UPSTATE NEW YORK INC.
- Site address
- 3063 COURT STREET
- City
- SYRACUSE
- State
- NY
- ZIP
- 13208
- Mailing
- 3063 COURT STREET, SYRACUSE, NY 13208
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424820
- Employees
- 300
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.23 C01
- Issued
- Feb 12, 2013
- Abate by
- Mar 17, 2013
- Penalty
- Initial $3,750 · Current $2,625 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent): a) Warehouse, Pick Modules, on or about 1/16/13: Open sided floors were not guarded along the 520, 530, 420 and 430 pick modules and empty pallet returns where numerous gates were left open, exposing employees to a fall hazard approximately 11 feet and 22 feet from floor level. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $2625
- — Z (S) $3750
1910.147 C06 I
- Issued
- Feb 12, 2013
- Abate by
- Mar 17, 2013
- Penalty
- Initial $2,250 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct an annual or more frequent inspection of the energy control procedure to ensure that the procedure and requirements of this standard were followed: a) At the establishment, on or about 1/22/13: There were no annual or periodic inspections conducted of the energy control procedures (lockout/tagout) to ensure that the procedures and requirements of the standard are being followed. Employees perform servicing and/or maintenance on various equipment, including, but not limited to conveyors, sorters, balers, air compressors, etc. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $1575
- — Z (S) $2250
1910.212 A01
- Issued
- Feb 12, 2013
- Penalty
- Initial $3,000 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: a) Maintenance Dept., on or about 1/16/13: Rotating chuck on a Dayton drill press was not guarded.
Recent events (2)
- — I (S) $2100
- — Z (S) $3000
1910.215 A04
- Issued
- Feb 12, 2013
- Penalty
- Initial $2,250 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch: A) Maintenance Area, on or about 1/16/13: The work rest on a Dayton bench grinder was not adjusted to 1/8 inch from the wheel.
Recent events (2)
- — I (S) $1575
- — Z (S) $2250
1910.215 B09
- Issued
- Feb 12, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: A) Maintenance Area, on or about 1/16/13: The tongue guards on a Dayton bench grinder were not adjusted to 1/4 inch from the wheel.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F01
- Issued
- Feb 12, 2013
- Abate by
- Feb 22, 2013
- Penalty
- Initial $2,250 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.303(f)(1): Each disconnecting means required by Subpart S of Part 1910 for motors and appliances was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Compressor Area, on or about 1/22/13: Two disconnect switches on the wall were not labeled as to what they controlled. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $1575
- — Z (S) $2250
1910.304 G05
- Issued
- Feb 12, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) Receiving Dock, on or about 1/16/13: Dock lights at door 206 and door 211 were not grounded in that the ground pin was missing from the plug ends. b) Shipping Dock, on or about 1/16/13: Dock light at door 110 was not grounded in that the ground pin was missing from the plug end.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Feb 12, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Warehouse, Pick Module, 530 area, on or about 1/16/13: An orange extension cord and a yellow extension cord providing current to radios were strung up from the level below and were being used as permanent wiring. b) Warehouse, Pick Module, 430 area, on or about 1/16/13: An orange extension cord providing current to a radio was strung up from the level below and was being used as permanent wiring. c) Warehouse, 320 Bottle Room, on or about 1/16/13: A yellow extension cord providing current to a water dispenser was being used as permanent wiring. d) Warehouse, 310 Bottle Room, on or about 1/16/13: An orange extension cord providing current to a fan was being used as permanent wiring.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 B02 I
- Issued
- Feb 12, 2013
- Abate by
- Mar 17, 2013
- Penalty
- Initial $3,000 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(i): The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 and did not make it available for inspection by the Assistant Secretary of Labor and his or her authorized representatives: a) At the establishment, on or about 1/22/13: There were no written safety related work practice procedures for employees performing various electrical equipment work. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $2100
- — Z (S) $3000
1910.22 A01
- Issued
- Feb 12, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition: a) Receiving Area, next to trash compactor: Area around the electrical service was not kept clean and orderly in that there were several gray breakage totes, boxes, a cart, bags of cans, etc. lying in the area.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B01 II
- Issued
- Feb 12, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Battery Charging Area near the Will Call Area, on or about 1/16/13: A circuit breaker panel labeled BC-2 had three blanks missing.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Southern Wine & Spirits of Upstate NEW York INC.
View Southern Wine & Spirits of Upstate NEW York INC.'s full OSHA safety record →
More inspections in this industry (NAICS 424820)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338291412.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.