Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: C B L ARCHITECTURAL FIBERGLASS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of C B L ARCHITECTURAL FIBERGLASS in 100 E. VALLEY, HERNANDO, MS 38632 (NAICS 325222). OSHA activity number 338313828.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch C B L Architectural Fiberglass — free Get an email when a new federal OSHA severe-injury report for C B L Architectural Fiberglass is published. One employer, no account, unsubscribe in one click.
Site address
100 E. VALLEY
City
HERNANDO
State
MS
ZIP
38632
Mailing
100 E. VALLEY, HERNANDO, MS 38632
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325222
Employees
20
Ownership type
A

3 citations on file for this inspection.

1910.107 C06

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 24, 2013
Abate by
Jun 11, 2013
Penalty
Initial $2,520 · Current $1,512 Reduced
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for     Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations:   (a) Paint Spray Area - On or about January 31, 2013 overhead lighting and electrical outlets were not approved for Class 1, Division 1 hazardous locations.  Employees spray painting XIM 400W White #1102 with a flash point of 55 degrees farienheit.
Recent events (2)
  • — I (S) $1512
  • — Z (S) $2520

1910.303 F02

Serious Gravity 1 1 instance 5 exposed
Issued
Apr 24, 2013
Abate by
May 20, 2013
Penalty
Initial $810 · Current $486 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:   (a) Grinding Area - On or about January 31, 2013 circuit breaker box was not labeled to indicate what each circuit breaker controls.
Recent events (2)
  • — I (S) $486
  • — Z (S) $810

1910.305 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 24, 2013
Abate by
May 20, 2013
Penalty
Initial $1,350 · Current $810 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    (a) Grinding Area - On or about January 31, 2013 circuit breaker box had numerous openings with missing breakers exposing employees to hazard of electrical shock.
Recent events (2)
  • — I (S) $810
  • — Z (S) $1350

View C B L Architectural Fiberglass's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338313828.