MILBRIDGE, ME —
OSHA Inspection: NARRAGUAGUS BAY HEALTH CARE FACILITY
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of NARRAGUAGUS BAY HEALTH CARE FACILITY in 3 MAIN STREET, MILBRIDGE, ME 04658 (NAICS 623110). OSHA activity number 338470248.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NARRAGUAGUS BAY HEALTH CARE FACILITY
- Site address
- 3 MAIN STREET
- City
- MILBRIDGE
- State
- ME
- ZIP
- 04658
- Mailing
- 3 MAIN STREET, MILBRIDGE, ME 04658
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 623110
- Employees
- 100
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.303 B02
- Issued
- Jun 26, 2013
- Abate by
- Jul 5, 2013
- Penalty
- Initial $2,100 · Current $1,365 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. Panel H-2 - 120V circuit breakers in slots 1a, 1b, 15a, 15b, 18a, & 18b were connected in pairs using copper wire in lieu of using three 220V breakers.
Recent events (2)
- — I (S) $1365
- — Z (S) $2100
1910.303 F02
- Issued
- Jun 26, 2013
- Abate by
- Jul 5, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. Panel H-2 - Circuits labeled 1 and 18 were labeled as heating circuits when they were spares.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B07
- Issued
- Jun 26, 2013
- Abate by
- Jul 9, 2013
- Penalty
- Initial $2,800 · Current $1,820 Reduced
General-duty citation text
29 CFR 1910.303(b)(7): Mechanical execution of work. Electric equipment shall be installed in a neat and workmanlike manner. Boiler Room - Energized wiring was not contained within boxes or fittings.
Recent events (2)
- — I (S) $1820
- — Z (S) $2800
1910.305 B03 II
- Issued
- Jun 26, 2013
- Abate by
- Jul 9, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(3)(ii): Boxes shall be closed by suitable covers securely fastened in place. Boiler Room - The junction box on the ceiling did not have its cover securely closed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Narraguagus BAY Health Care Facility
View Narraguagus BAY Health Care Facility's full OSHA safety record →
More inspections in this industry (NAICS 623110)
More inspections in ME
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338470248.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.