OSHA Inspection: PROTEIN PRODUCTS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PROTEIN PRODUCTS, INC. in 1042 HIGHWAY 3, SUNFLOWER, MS 38778 (NAICS 311613). OSHA activity number 338474836.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Protein Products, INC. — free Get an email when a new federal OSHA severe-injury report for Protein Products, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1042 HIGHWAY 3
City
SUNFLOWER
State
MS
ZIP
38778
Mailing
1042 HIGHWAY 3 NORTH, SUNFLOWER, MS 38778
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311613
Employees
70
Ownership type
A

10 citations on file for this inspection.

1910.151 C

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 14, 2013
Abate by
Apr 9, 2013
Penalty
Initial $2,800 · Current $1,680 Reduced
29 CFR 1910.151(c):     Where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use.  [63 FR 33450, June 18, 1998]    Chicken Staging Area - On or about January 17, 2013, employees were using a corrosive high foam soap to clean the chicken dock. Employees were not provided an emergency eye wash for quick drenching or flushing of the eyes.
Recent events (2)
  • — I (S) $1680
  • — Z (S) $2800

1910.157 C01

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 14, 2013
Penalty
Initial $2,100 · Current $1,260 Reduced
29 CFR 1910.157(c)(1):     The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury.    Production Area - On or about January 17, 2013, several fire extinguishers were missing and/or not properly mounted throughout the production area.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.157 E03

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 14, 2013
Abate by
Apr 9, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3):     The employer shall assure that portable fire extinguishers are subjected to an annual maintenance check. Stored pressure extinguishers do not require an internal examination. The employer shall record the annual maintenance date and retain this record for one year after the last entry or the life of the shell, whichever is less. The record shall be available to the Assistant Secretary upon request.      Facility - On or about Janaury 17, 2013 the employer had not conducted an annual maintenance check on the portable fire extinguishers.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.219 C04 I

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 14, 2013
Abate by
Apr 9, 2013
Penalty
Initial $2,100 · Current $1,260 Reduced
29 CFR 1910.219(c)(4)(i):     Projecting shaft ends shall present a smooth edge and end and shall not project more than one-half the diameter of the shaft unless guarded by nonrotating caps or safety sleeves.      Front Loading Area - On or about January 17, 2013 a 2 inch shaft on the IPEC machine was projecting 1 1/2 inches without a safety guard.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.219 F03

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 14, 2013
Abate by
Apr 9, 2013
Penalty
Initial $2,625 · Current $1,575 Reduced
29 CFR 1910.219(f)(3):     Sprockets and chains. All sprocket wheels and chains shall be enclosed unless they are more than seven (7) feet above the floor or platform. Where the drive extends over other machine or working areas, protection against falling shall be provided. This subparagraph does not apply to manually operated sprockets.      Front Loading Area - On or about January 17, 2013 the moving chain on the IPEC machine was 60 inches above the ground and was not enclosed by a guard.
Recent events (2)
  • — I (S) $1575
  • — Z (S) $2625

1910.254 D09 III

Serious Gravity 1 1 instance 1 exposed
Issued
Mar 14, 2013
Penalty
Initial $1,575 · Current $945 Reduced
29 CFR 1910.254(d)(9)(iii):     Cables with damaged insulation or exposed bare conductors shall be replaced. Joining lengths of work and electrode cables shall be done by the use of connecting means specifically intended for the purpose. The connecting means shall have insulation adequate for the service conditions.   [55 FR 13709, Apr. 11, 1990; 61 FR 9227, March 7, 1996; 70 FR 53929, Sept. 13, 2005]      Main Production Area - On or about January 17, 2013 welding cables on the Bobcat 250 portable welding machine were damaged.
Recent events (2)
  • — I (S) $945
  • — Z (S) $1575

1910.303 F02

Serious Gravity 1 1 instance 1 exposed
Issued
Mar 14, 2013
Penalty
Initial $2,100 · Current $1,260 Reduced
29 CFR 1910.303(f)(2):     Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident.      Main Disconnect for Baler - On or about January 18, 2013 the electrical panel box was not labeled.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.303 G02 I

Serious Gravity 1 1 instance 1 exposed
Issued
Mar 14, 2013
Penalty
Initial $2,100 · Current $1,260 Reduced
29 CFR 1910.303(g)(2)(i):     Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidentalcontact by use of approved cabinets or other forms of approved enclosures or by any of the following means:      Electrical Room - On or about January 17, 2013 front cvers were missing from the electrical panels.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.253 A03

Other-than-serious 1 instance 2 exposed
Issued
Mar 14, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.253(a)(3):     Apparatus. Only approved apparatus such as torches, regulators or pressure-reducing valves, acetylene generators, and manifolds shall be used.    Main Production Area - On or about January 17, 2013 the pressure gauge on the oxygen and actelyne cylinders used with the mobile welding machine was damaged.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 B07 I

Other-than-serious 1 instance 1 exposed
Issued
Mar 14, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i):     Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment.      Engagement Hallway - On or about January 17, 2013 a breaker was missing from the panel box and the opening was not closed or covered.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Protein Products, INC.'s full OSHA safety record →