Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CREEK ELECTRIC INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CREEK ELECTRIC INC. in 715 E. 13TH ST., WICHITA, KS 67214 (NAICS 238210). OSHA activity number 338488430.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Creek Electric INC. — free Get an email when a new federal OSHA severe-injury report for Creek Electric INC. is published. One employer, no account, unsubscribe in one click.
Establishment
CREEK ELECTRIC INC.
Site address
715 E. 13TH ST.
City
WICHITA
State
KS
ZIP
67214
Mailing
2811 W. PAWNEE, WICHITA, KS 67213
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
1
Ownership type
A

3 citations on file for this inspection.

1910.333 B02 III A

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
May 8, 2013
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.333(b)(2)(iii)(A): A lock and a tag shall be placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed, except as provided in paragraphs (b)(2)(iii)(C) and (b)(2)(iii)(E) of this section. The lock shall be attached so as to prevent persons from operating the disconnecting means unless they resort to undue force or the use of tools.  On or about January 23, 2013 employee(s) preparing to remove, inspect and replace an 800 amp breaker in the B mill motor control room were exposed to electrocution, electrical shock, and arc flash explosion hazards due to no lock and tag being applied to the appropriate disconnecting means.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4900

1910.333 B02 IV B

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
May 8, 2013
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.333(b)(2)(iv)(B): A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately after this test.  On or about January 23, 2013:  Employee(s) engaged in breaker inspection and replacements activities at the B Mill motor control center were exposed to electrical shock, electrocution and arc flash explosion hazards in that the circuit elements and the electrical components were not tested to ensure the electrical power was properly deenergized prior to beginning work.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4900

1910.335 A01 I

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
May 8, 2013
Penalty
Initial $4,200 · Current $0 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.   On or about January 23, 2013, employee(s) were exposed to electrocution, electrical shock and arc flash explosion hazards due to inadequate personal protective equipment, such as no face shield and non-electrically rated hand protection, being worn while removing, inspecting and replacing an 800 amp breaker in the B mill motor control center.