IDAHO FALLS, ID ·
OSHA Inspection: BRAND X EQUIPMENT, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BRAND X EQUIPMENT, LLC in 1615 N. WOODRUFF AVE, IDAHO FALLS, ID 83401 (NAICS 532490). OSHA activity number 338519432.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BRAND X EQUIPMENT, LLC
- Site address
- 1615 N. WOODRUFF AVE
- City
- IDAHO FALLS
- State
- ID
- ZIP
- 83401
- Mailing
- 1615 N. WOODRUFF AVE, IDAHO FALLS, ID 83401
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 532490
- Employees
- 7
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.37 A02
- Issued
- Feb 4, 2013
- Penalty
- Initial $1,200 · Current $840 Reduced
General-duty citation text
29 CFR 1910.37(a)(2): Exit routes were arranged so that employees would have to travel toward a high hazard area: (a) Shop Area: On 01/22/13 and at times prior thereto, four fuel containers with residual amounts of fuel and one approximately half full were stored along the route to the southeast exit door. NOTE: Abatement certification IS NOT required for this item.
Recent events (2)
- · I (S) $840
- · Z (S) $1200
1910.303 F02
- Issued
- Feb 4, 2013
- Abate by
- Mar 22, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: (a) Retail/Showroom area: on 1/22/13 and at times prior thereto, the indexes for two circuit panels were not accurate and/or complete. NOTE: Abatement certification IS required for this item.
Recent events (2)
- · I (O) $0
- · Z (O) $0
1910.305 B01 II
- Issued
- Feb 4, 2013
- Abate by
- Mar 22, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) Retail/Showroom Area: On 1/22/13 and at times prior thereto, on side-by-side panels, the right panel did not have a circuit breaker or cover installed at position 11. NOTE: Abatement certification IS required for this item.
Recent events (2)
- · I (O) $0
- · Z (O) $0
1910.305 B02 I
- Issued
- Feb 4, 2013
- Abate by
- Mar 22, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: (a) Storage Room: on 1/22/13 and at times prior thereto, two outlet boxes were missing covers. NOTE: Abatement certification IS required for this item.