OSHA Inspection: JOHNS MANVILLE CORPORATION

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of JOHNS MANVILLE CORPORATION in 600 JAYCEE DRIVE VALMONT INDUSTRIAL PARK, HAZLETON, PA 18202 (NAICS 326150). OSHA activity number 338519630.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Johns Manville Corporation — free Get an email when a new federal OSHA severe-injury report for Johns Manville Corporation is published. One employer, no account, unsubscribe in one click.
Site address
600 JAYCEE DRIVE VALMONT INDUSTRIAL PARK
City
HAZLETON
State
PA
ZIP
18202
Mailing
600 JAYCEE DRIVE VALMONT INDUSTRIAL PARK, HAZLETON, PA 18202
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326150
Employees
65
Ownership type
A

3 citations on file for this inspection.

1910.119 L04

Serious Gravity 1 2 instances 2 exposed
Issued
Apr 8, 2013
Abate by
May 11, 2013
Penalty
Initial $2,250 · Current $2,250
29 CFR 1910.119(l)(4):     Process safety information was not updated accordingly after a change in the process covered by this paragraph:  a) Pentane System: The piping and instrument diagram (P&ID)(PSM-PID-004) and the electrical classification diagram (Drawing #177040-2) were not updated to reflect changes in the pentane system that had occurred under Management of Change (MOC) #10190902, as observed on or about January 31, 2013.  Abatement Certification Required.
Recent events (2)
  • — I (S) $2250
  • — Z (S) $2250

1910.119 E03 I

Serious Gravity 1 1 instance 2 exposed
Issued
Apr 8, 2013
Abate by
May 11, 2013
Penalty
Initial $2,250 · Current $0 Reduced
29 CFR 1910.119(e)(3)(i):     The process hazard analysis did not address the hazards of the process:  a) Pentane System: The process hazard analysis did not address potential hazards to system including the removal of the storage tank fire insulation and the storage tank enclosure, as observed on or about January 31, 2013.  Abatement Certification Required.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2250

1910.119 F01

Serious Gravity 1 1 instance 2 exposed
Issued
Apr 8, 2013
Abate by
May 11, 2013
Penalty
Initial $2,250 · Current $1,500 Reduced
29 CFR 1910.119(f)(1):     The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information:  a) Pentane System: The employer did not develop a written operating procedure for the by pass of LFL controls during calibration of the LFL sensors, as observed on or about January 31, 2013.  Abatement Certification Required.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2250

View Johns Manville Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338519630.