Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ADVANCED DESIGN & CONSTRUCTION COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ADVANCED DESIGN & CONSTRUCTION COMPANY in 1100 VERMONT AVE., NW, WASHINGTON, DC 20006 (NAICS 236210). OSHA activity number 338586241.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Advanced Design & Construction Company — free Get an email when a new federal OSHA severe-injury report for Advanced Design & Construction Company is published. One employer, no account, unsubscribe in one click.
Site address
1100 VERMONT AVE., NW
City
WASHINGTON
State
DC
ZIP
20006
Mailing
386 EAST MAPLE AVE., SUITE 101, VIENNA, VA 22180
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236210
Employees
5
Ownership type
A

2 citations on file for this inspection.

1926.403 I02 I

Other-than-serious 1 instance 5 exposed
Issued
Jun 6, 2013
Abate by
Jun 18, 2013
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraph's (A) through (D) of this paragraph:      11th. Floor Elevator Lobby - A Federal Pacific service distribution paned board had five missing circuit breakers thereby exposing workers to a 120 volt electrical contact hazards, on or about 01/29/2013.     Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.     This contractor was the Exposing and Controlling employer pursuant to the Occupational Safety & Health Administration's Multi-Employer Work site Policy.
Recent events (2)
  • — I (O) $1750
  • — Z (S) $3500

1926.403 I01 II

Other-than-serious 1 instance 5 exposed
Issued
Jun 6, 2013
Abate by
Jun 16, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.403(i)(1)(ii): Working space about electric equipment operating at 600 volts, nominal, or less was used for storage:     11th Floor Elevator Lobby - Large stacks of roof insulation panels were stored immediately in front of and surrounding a Federal Pacific circuit distribution panel thereby was completely blocking instant access to the electrical equipment, on or about 01/29/2013.      Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.     This contractor was both the Exposing and Controlling employer under the Occupational Safety & Health Administration's Multi-Employer Work site Policy.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View Advanced Design & Construction Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338586241.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.