Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: JUNE ELECTRIC CORP.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of JUNE ELECTRIC CORP. in 47 EAST 34TH ST., NEW YORK, NY 10016 (NAICS 541350). OSHA activity number 338624232.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch June Electric Corp. — free Get an email when a new federal OSHA severe-injury report for June Electric Corp. is published. One employer, no account, unsubscribe in one click.
Establishment
JUNE ELECTRIC CORP.
Site address
47 EAST 34TH ST.
City
NEW YORK
State
NY
ZIP
10016
Mailing
209 HILLSIDE AVE., WILLISTON PARK, NY 11596
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541350
Employees
2
Ownership type
A

5 citations on file for this inspection.

1910.332 B01

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 30, 2013
Abate by
Aug 9, 2013
Penalty
Initial $3,080 · Current $3,080
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments.     a) Roof bulkhead electrical room:     An employee was installing metal cover on an energized bus duct riser and was injured by an arc explosion. Injured employee was not trained in and familiar with the safety-related work practices that pertained to working on energized bus duct risers. On or about 01/31/13.     NOTE:  IN ADDITION TO CERTIFICATION OF ABATEMENT, THE EMPLOYER IS REQUIRED TO SUBMIT DOCUMENTATION OF ABATEMENT FOR THIS ITEM.  FAILURE TO COMPLY MAY RESULT IN AN ADDITIONAL PENALTY OF $1,000 AS PER 29 CFR 1903.19.
Recent events (1)
  • — Z (S) $3080

1910.333 C02

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 30, 2013
Abate by
Aug 9, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.     a) Roof bulkhead electrical room:     An employee was installing metal cover on an energized bus duct riser and was injured by an arc explosion. Injured employee was not familiar with and not qualified to work on energized bus duct risers. The employer did not ensure only qualified employees were working on energized bus duct risers. On or about 01/31/13.     NOTE:  IN ADDITION TO CERTIFICATION OF ABATEMENT, THE EMPLOYER IS REQUIRED TO SUBMIT DOCUMENTATION OF ABATEMENT FOR THIS ITEM.  FAILURE TO COMPLY MAY RESULT IN AN ADDITIONAL PENALTY OF $1,000 AS PER 29 CFR 1903.19.
Recent events (1)
  • — Z (S) $0

1910.333 A02

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 30, 2013
Abate by
Aug 9, 2013
Penalty
Initial $3,080 · Current $3,080
29 CFR 1910.333(a)(2): Where exposed live parts were not de-energized, other safety related work practices were not used to protect employees who could be exposed to the electrical hazards involved.     a) Roof bulkhead electrical room:     An employee was installing metal cover on an energized bus duct riser and was injured by an arc explosion. Safety related work practices were not used to protect employees who were exposed to the electrical hazards involved in working on energized bus duct risers with exposed live parts. On or about 01/31/13.     NOTE:  IN ADDITION TO CERTIFICATION OF ABATEMENT, THE EMPLOYER IS REQUIRED TO SUBMIT DOCUMENTATION OF ABATEMENT FOR THIS ITEM.  FAILURE TO COMPLY MAY RESULT IN AN ADDITIONAL PENALTY OF $1,000 AS PER 29 CFR 1903.19.
Recent events (1)
  • — Z (S) $3080

1910.335 A01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 30, 2013
Abate by
Aug 9, 2013
Penalty
Initial $3,080 · Current $3,080
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed.     a) Roof bulkhead electrical room:     An employee was installing metal cover on an energized bus duct riser and was injured by an arc explosion. Injured employee was not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for working on energized bus duct risers. On or about 01/31/13.     NOTE:  IN ADDITION TO CERTIFICATION OF ABATEMENT, THE EMPLOYER IS REQUIRED TO SUBMIT DOCUMENTATION OF ABATEMENT FOR THIS ITEM.  FAILURE TO COMPLY MAY RESULT IN AN ADDITIONAL PENALTY OF $1,000 AS PER 29 CFR 1903.19.
Recent events (1)
  • — Z (S) $3080

1910.335 A01 V

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 30, 2013
Abate by
Aug 9, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face:     a) Roof bulkhead electrical room:     An employee was installing metal cover on an energized bus duct riser and suffered injuries to the eyes and face by an arc explosion. Injured employee was not provided with, and did not wear electrical protective equipment for the eyes and face. On or about 01/31/13.     NOTE:  IN ADDITION TO CERTIFICATION OF ABATEMENT, THE EMPLOYER IS REQUIRED TO SUBMIT DOCUMENTATION OF ABATEMENT FOR THIS ITEM.  FAILURE TO COMPLY MAY RESULT IN AN ADDITIONAL PENALTY OF $1,000 AS PER 29 CFR 1903.19.
Recent events (1)
  • — Z (S) $0

View June Electric Corp.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338624232.