OSHA Inspection: METTENBRINK ELECTRIC CORP

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of METTENBRINK ELECTRIC CORP in 3445 STOLLEY PARK ROAD, GRAND ISLAND, NE 68802 (NAICS 238210). OSHA activity number 338658230.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mettenbrink Electric Corp — free Get an email when a new federal OSHA severe-injury report for Mettenbrink Electric Corp is published. One employer, no account, unsubscribe in one click.
Site address
3445 STOLLEY PARK ROAD
City
GRAND ISLAND
State
NE
ZIP
68802
Mailing
PO BOX 548, GRAND ISLAND, NE 68802
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
6
Ownership type
A

4 citations on file for this inspection.

1910.132 D02

Serious Gravity 5 3 instances 5 exposed
Issued
Apr 18, 2013
Abate by
May 31, 2013
Penalty
Initial $2,000 · Current $1,000 Reduced
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification which included the requirements as outlined in 29 CFR 1910.132(d)(2):(a)(LOCATION)(IDENTIFY SPECIFIC OPERATION(S) AND/OR CONDITIONS)(DESCRIBE HAZARD(S) WHERE NECESSARY)     The employer failed to conduct hazard assessments prior to exposing employees to potential electrical hazards associated with employees working on high voltage electrical wiring without wearing the appropriate personnel protective equipment that meets the requirements of  NFPA 70E and required by Subpart I of this part.  This was most recently evident during the inspection of the facility located at 3445 Stolley Park Road, Grand Island, NE 68802, where the employer has an employee wiring in a Miller wire welder into an existing bus box with live exposed parts without requiring that they de-energize and lockout the bus bar or wear the necessary personnel protective equipment to prevent an employee from being injured in the event of an arc flash as demonstrated in this accident.  Instances of personnel protective equipment include but are not limited to:    i.   Employee working on the bus box without wearing arc flash protective jacket or pants to protect  body.  ii.  Employee working on the bus box without wearing arc flash protective hood and helmet to protect face, neck and head.  iii. Employees working on the bus box without wearing arc flash protective gloves to protect hands.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.147 C07 IV

Deleted Serious Gravity 5 1 instance 5 exposed
Issued
Apr 18, 2013
Abate by
May 23, 2013
Penalty
Initial $2,000 · Current $0 Reduced
29 CFR 1910.147(c)(7)(iv): The employer did not certify that employee training had been accomplished and kept up to date:(a) (LOCATION) (IDENTIFY SPECIFIC OPERATIONS AND/OR CONDITIONS) (IDENTIFY MACHINERY OR EQUIPMENT) (DESCRIBE WHETHER LACK OF TRAINING, OR NOT KEPT UP TO DATE, OR BOTH)   The employer failed to certify that authorized lockout and tag out employees were trained in accordance with this subpart on the potential electrical and stored energy hazards associated with employees working on high voltage electrical wiring and the application of locks and tags used in maintaining de-energized equipment.  This was most recently evident during the inspection of the facility located at 3445 Stolley Park Road, Grand Island, NE 68802, where the employer has an employee for whom he has no certification to demonstrate what training he has received, wiring in a Miller wire welder into an existing bus box on a live bus bar system without locking out the live bus bar first.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2000

1910.333 B02

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 18, 2013
Abate by
May 31, 2013
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2):     The employer failed to protect employees from potential electrical hazards associated with employees working on high voltage electrical wiring without locking out and or tagging out the live energy source to the equipment they were working on.  This was most recently evident during the inspection of the facility located at 3445 Stolley Park Road, Grand Island, NE 68802, where the employer has an employee wiring in a Miller wire welder into an existing bus box with live exposed parts without requiring that they de-energize and lockout the bus bar.
Recent events (2)
  • — I (S) $1960
  • — Z (S) $2800

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 18, 2013
Abate by
May 31, 2013
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:(a) (LOCATION) (IDENTIFY SPECIFIC OPERATIONS AND/OR CONDITIONS)     The employer failed to protect employees from potential electrical hazards associated with employees working on high voltage electrical wiring without wearing the appropriate personnel protective equipment that meets the requirements of  NFPA 70E and required by Subpart I of this part.  This was most recently evident during the inspection of the facility located at 3445 Stolley Park Road, Grand Island, NE 68802, where the employer has an employee wiring in a Miller wire welder into an existing bus box with live exposed parts without requiring that they de-energize and lockout the bus bar or wear the necessary personnel protective equipment to prevent an employee from being injured in the event of an arc flash as demonstrated in this accident.  Instances of personnel protective equipment include but are not limited to:        i.   Employee working on the bus box without wearing arc flash protective jacket or pants to protect body.   ii.  Employee working on the bus box without wearing arc flash protective hood and helmet to protect face, neck and head.   iii. Employees working on the bus box without wearing arc flash protective gloves to protect hands.
Recent events (2)
  • — I (S) $2800
  • — Z (S) $2800

View Mettenbrink Electric Corp's full OSHA safety record →