GLASGOW, WV —
OSHA Inspection: RJ RECYCLING, LLC
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of RJ RECYCLING, LLC in ROUTE 60, GLASGOW, WV 25086 (NAICS 423930). OSHA activity number 338659642.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RJ RECYCLING, LLC
- Site address
- ROUTE 60
- City
- GLASGOW
- State
- WV
- ZIP
- 25086
- Mailing
- P.O. BOX 531, GLASGOW, WV 25086
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423930
- Employees
- 9
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.305 G01 IV A
- Issued
- Mar 26, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) Small Scale Area: A Dayton gas heater with electric ignition was provided electric power by splicing the power cord onto a plug attachment that was then plugged into an extension cord as observed on November 4, 2013.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 B02
- Issued
- Mar 26, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Small Scale Area: A Dayton gas heater with electric ignition that was designed to be hard wired into a power source was provided electric power by splicing the power cord onto a plug attachment as observed on November 4, 2013.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1904.32 A04
- Issued
- Mar 26, 2013
- Penalty
- Initial $700 · Current $525 Reduced
General-duty citation text
29 CFR 1904.32(a)(4): The employer did not post an OSHA 300A Form or equivalent by February 1 thru April 30. (a) The 2012 annual summary of injuries and illnesses had not been posted reflecting one recordable injury for the year as observed on February 4, 2013.
Recent events (2)
- — I (O) $525
- — Z (O) $700
More inspections at RJ Recycling, LLC