FORT COLLINS, CO —
OSHA Inspection: CORIX UTILITIES, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CORIX UTILITIES, INC. in 155 E. BOARDWALK DRIVE, FORT COLLINS, CO 80525 (NAICS 237130). OSHA activity number 338685068.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CORIX UTILITIES, INC.
- Site address
- 155 E. BOARDWALK DRIVE
- City
- FORT COLLINS
- State
- CO
- ZIP
- 80525
- Mailing
- 11020 W. PLANK CT. STE 100, WAUWATOSA, WI 53226
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237130
- Employees
- 28
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.21 B02
- Issued
- Jul 3, 2013
- Abate by
- Jul 10, 2014
- Penalty
- Initial $7,000 · Current $2,000 Reduced
General-duty citation text
29 CFR 1926.21(b)(2): The employer shall instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his work environment to control or eliminate any hazards or other exposure to illness or injury. On or about March 1, 2013, an employee was unaware of the exact fabric makeup of the undergarments he was wearing while working for the employer on the employer on the employer on January 16, 2013.
Recent events (3)
- — F (O) $2000
- — C (S) $7000
- — Z (S) $7000
1910.335 A02 II
- Issued
- Jul 3, 2013
- Abate by
- Jul 24, 2013
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(2)(ii): Protective shields, protective barriers, or insulating materials shall be used to protect each employee from shock, burns, or other electrically related injuries while that employee is working near exposed energized parts which might be accidentally contated or where dangerous electric heating or arcing might occur: (a) Corix Utilities, Inc. @ 155 E. Boardwalk Dr., Fort Collins, CO 80525: On and before January 16th, 2013, the employer did not ensure that employees were fully protected from arc flash injuries by the use of protective shields, barriers or insulating materials during the removal and installation of an electric meter. On January 16th, 2013, an employee was inserting a new AMI electrical meter into a meter socket involving 277/480V switchgear with the load and line energized, when an arc flash/blast occurred. The employee received burns to the ears and head as a result. This condition exposed employees to burns associated with arc flash and arc blast incidents. An acceptable abatement method would be to incorporate the use of protective shields, protective barriers or insulative materials that fully protect the employee from hazardous energy, including thermal energy. Another feasible and acceptable method of abatement may be achieved through compliance found in the National Fire Protection Association (NFPA) 70E, 2012 Edition, Section 10(b)(1) Head Protection, instructs individuals: "An arc-rated balaclava shall be used with an arc-rated face-shield when the back of the head is within the arc flash boundary." Table 130.7(C)(16) categorize the activities into risk groups, and describe protective clothing and personal protective equipment associated for each group. This criteria also provides that if the meter technicians are working with voltages over 240V, the PPE should satisfy an arc-rating of 8 cal/cm2 based on the Hazard/Risk Category2*. An arc-rated flash suit hood or arc-rated face shield and arc-rated balaclava are required for Hazard/Risk Category 2 activities. OR IN THE ALTERNATIVE Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to burn injuries from arc flash/blast while removing or installing meters and exposed to energized electrical equipment over 240V. (a) Corix Utilities, Inc. @ 155 E. Boardwalk Dr., Fort Collins, CO 80525: On and before January 16th, 2013, the employer did not ensure employees were protected from thermal energy hazards created by arc flash/blast during removal and installation of an electric meter. On January 16th, 2013, an employee was inserting a new AMI electrical meter into a meter socket involving 277/480V switchgear with the load and line energized when an arc flash/blast occurred. The employee received burns to the ears and head as a result. This condition exposed employees to burns associated with arc flash and arc blast incidents. One feasible and acceptable method of abatement may be achieved through compliance found in the National Fire Protection Association (NFPA) 70E, 2012 Edition, Section 10(b)(1) Head Protection, instructs individuals: "An arc-rated balaclava shall be used with an arc-rated face-shield when the back of the head is within the arc flash boundary." Table 130.7(C)(16) categorize the activities into risk groups, and describe protective clothing and personal protective equipment associated for each group. This criteria also provides that if the meter technicians are working with voltages over 240V, the PPE should satisfy an arc-rating of 8 cal/cm2 based on the Hazard/Risk Category2*. An arc-rated flash suit hood or arc-rated face shield and arc-rated balaclava are required for Hazard/Risk Category 2 activities.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
More inspections in this industry (NAICS 237130)
More inspections in CO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338685068.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.