OSHA Inspection: U.S. CUSTOMS AND BORDER PROTECTION-SAN JUAN LABORATORY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. CUSTOMS AND BORDER PROTECTION-SAN JUAN LABORATORY in 1 LA PUNTILLA STREET, ROOM 125, SAN JUAN, PR 00901 (NAICS 928110). OSHA activity number 338734841.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Customs and Border Protection-San Juan Laboratory — free Get an email when a new federal OSHA severe-injury report for U.S. Customs and Border Protection-San Juan Laboratory is published. One employer, no account, unsubscribe in one click.
Site address
1 LA PUNTILLA STREET, ROOM 125
City
SAN JUAN
State
PR
ZIP
00901
Mailing
1 LA PUNTILLA STREET, ROOM 125, SAN JUAN, PR 00901
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
15
Ownership type
D

6 citations on file for this inspection.

1910.253 B01 II

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 23, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(1)(ii): Compressed gas cylinders shall be legibly marked, for the purpose of identifying the gas content, with either the chemical or the trade name of the gas. Such marking shall be by means of stenciling, stamping, or labeling, and shall not be readily removable. Whenever practical, the marking shall be located on the shoulder of the cylinder:   On or about 02/06/13, at 1 La Puntilla Street, Room 125, San Juan, PR, in the flammable storage area, a compressed gas cylinder was accepted for use and did not legibly identify its content by name.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS NOT REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 4 instances 15 exposed
Issued
Apr 23, 2013
Abate by
May 17, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):   Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:   a) On or about 02/06/13, at 1 La Puntilla Street, Room 125, San Juan, PR, in the Petroleum room area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   b) On or about 02/06/13, at 1 La Puntilla Street, Room 125, San Juan, PR, in the Petroleum room area, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle.   c) On or about 02/06/13, at 1 La Puntilla Street, Room 125, San Juan, PR, in the Petroleum room area, a ground-fault circuit interrupter was not installed in all 125-volt, single phase, 15-and 20-ampere receptacles installed within 6 feet or 1.8 meters of the outside edge of a sink.   d) On or about 02/06/13, at 1 La Puntilla Street, Room 125, San Juan, PR, in the wet chemistry room area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.303 F02

Serious Gravity 1 1 instance 15 exposed
Issued
Apr 23, 2013
Abate by
May 17, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2):   Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident:  On or about 02/06/13, at 1 La Puntilla, Room 125, San Juan, PR, the circuit breakers or fuses in the electrical panel, that service the laboratory lounge and the  laboratory A/C unit, were not identified or labeled to show the locations of the building whose circuits they protect.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 23, 2013
Abate by
May 17, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i):   All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:  On or about 02/06/13, at 1 La Puntilla Street, Room 125, San Juan, PR, in the forensics room area, an electrical outlet box was not covered or closed.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV C

Serious Gravity 1 2 instances 3 exposed
Issued
Apr 23, 2013
Abate by
May 17, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(C):   Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where run through doorways, windows, or similar openings:   On or about 02/06/13, at 1 La Puntilla Street, Room 125, San Juan, PR, in the forensics room area, the flexible cords of the relocatable power taps were run through holes between the cabinet countertops and the walls.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.1200 E01 I

Other-than-serious 1 instance 15 exposed
Issued
Apr 23, 2013
Abate by
May 17, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(e)(1)(i): A list of the hazardous chemicals known to be present using a product identifier that is referenced on the appropriate safety data sheet (the list may be compiled for the workplace as a whole or for individual work areas):   On or about 02/06/13, at 1 La Puntilla Street, Room 125, San Juan, PR, a list, index or inventory of the hazardous chemicals in the workplace for which material safety data sheets should be available was not included in the hazard communication program.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.